DELCON
The relays are used as interfaces between control systems and DC loads. The relays handle inductive loads and high DC voltages with low load reduction compared to mechanical relays, which provide a long lifetime. If a diode is mounted across a load, such as 1N4007, the nominal current applies, even with high inductive loads. (Keep in mind that the drop-out time increases when mounting a diode.) The relays have no mechanical parts, which means very reliable application. The integrated interference protection provides reliable operation even in very demanding electrical environments. Thanks to interference protection, signal cables can be run alongside power cables on, for example, cable racks for more than 1.5 km without capacitive cross-talk affecting relays.
Input data |
|
---|---|
Input current at nominal voltage, typ | 12 mA |
Input current at nominal voltage, max | 15 mA |
Response time | 0,3 ms |
Release time | 0,3 ms |
Control voltage dc min | 18 V |
Control voltage dc max | 32 V |
Switching voltage | 16 V |
Turn-off voltage | 14 V |
Input impedance, typ | 2 kΩ |
Input voltage nom | 24 |
Output data |
|
Number of poles | 1 |
Load current | 3 A |
Leakage current | 1 mA |
*Invisible Heading* |
|
---|---|
Peak current | 15 A (10 ms) A |
Load voltage dc max | 60 V |
Voltage drop | 0,5 V |
General data |
|
Width | 12,5 mm |
Temperature operational min | -40 °C |
Temperature operational max | 70 °C |
Storage temperature min | -40 °C |
Storage temperature max | 70 °C |
Colour | Red |
Material | PBT |
Weight | 40 g |
Approvals | CE, UL |
The relays are used as interfaces between control systems and DC loads. The relays handle inductive loads and high DC voltages with low load reduction compared to mechanical relays, which provide a long lifetime. If a diode is mounted across a load, such as 1N4007, the nominal current applies, even with high inductive loads. (Keep in mind that the drop-out time increases when mounting a diode.) The relays have no mechanical parts, which means very reliable application. The integrated interference protection provides reliable operation even in very demanding electrical environments. Thanks to interference protection, signal cables can be run alongside power cables on, for example, cable racks for more than 1.5 km without capacitive cross-talk affecting relays.
Renowned for high-quality cable cutting and crimping tools, Klauke serves electrical contractors, cable jointers, and linemen across a spectrum of sectors
At OEM Automatic, we can supply a series of components for your one project. All under one roof. This case study discusses how we supplied several components for our customer's new electro-pneumatic control box.
To promote constant and reliable performance, as well as a longer life of parts in the vehicle, it is important to consider the right cable protector.
We have now added switch disconnectors to our range! Switch disconnectors contribute to the overall functionality and safety of electrical systems.
LOCC-Box from Lutze is an intelligent current monitoring device that provides reliable protection of DC circuits in a slimline 8.1mm housing.
OEM Automatic has integrated push-in technology into it's product offering for many years now. In this blog post, we'll explore the various benefits of push-in technology and some of the products we offer that make use of this innovation, such as push-in terminals, push-in sockets, and even push-in heaters.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Input current at nominal voltage, typ | Input current max | Input current at nominal voltage, max | Response time | Release time | Control voltage dc min | Control voltage dc max | Switching voltage | Turn-off voltage | Input impedance, typ | Input voltage nom | Load current | Leakage current | Peak current | Load voltage dc max | Voltage drop | Temperature operational min | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
O/P Plug-in Relay 5V dc / 0-60V dc 3A
Art:
SLO5CR
Copied
|
12 mA
|
|
15 mA
|
0,3 ms
|
0,3 ms
|
3 V
|
7 V
|
2,7 V
|
2,5 V
|
0,42 kΩ
|
5
|
3 A
|
|
15 A (10ms) A
|
60 V
|
0,5 V
|
-40 °C
|
| ||
O/P Plug-in Relay 24V dc / 0-60V dc 3A
Art:
SLO24CR
Copied
|
12 mA
|
|
15 mA
|
0,3 ms
|
0,3 ms
|
18 V
|
32 V
|
16 V
|
14 V
|
2 kΩ
|
24
|
3 A
|
1 mA
|
15 A (10 ms) A
|
60 V
|
0,5 V
|
-40 °C
|
| ||
O/P Plug-in Relay 24V dc / 0-24V dc 10A
Art:
SLO24CRX
Copied
|
12 mA
|
|
15 mA
|
0,3 ms
|
0,3 ms
|
18 V
|
32 V
|
16 V
|
14 V
|
2 kΩ
|
24
|
10 A
|
1 mA
|
80 A (10ms) A
|
32 V
|
0,3 V
|
-40 °C
|
| ||
O/P Plug-in Relay 24V dc / 0-250V dc 1.8A
Art:
SLO24CRA
Copied
|
12 mA
|
|
15 mA
|
0,3 ms
|
0,3 ms
|
18 V
|
32 V
|
16 V
|
14 V
|
2 kΩ
|
24
|
1,8 A
|
1 mA
|
12 A (10 ms) A
|
250 V
|
1 V
|
-40 °C
|
| ||
Art:
SLO48CRA5
Copied
|
9 mA
|
|
12 mA
|
0,3 ms
|
0,3 ms
|
35 V
|
60 V
|
30 V
|
7 V
|
1,3 kΩ
|
48
|
5 A
|
1 mA
|
20 A (10 ms) A
|
350 V
|
0,6 V
|
-25 °C
|
| ||
O/P Plug-in Relay 120V dc / 0-250V dc 1.8A
Art:
SLO120CRA
Copied
|
3,5 mA
|
4 mA
|
|
0,5 ms
|
0,5 ms
|
95 V
|
140 V
|
80 V
|
60 V
|
34 kΩ
|
120
|
1,8 A
|
1 mA
|
12 A (10ms) A
|
250 V
|
1 V
|
-25 °C
|
| ||
O/P Plug-in Relay 220V dc / 0-250V dc 1.8A
Art:
SLO220CRA
Copied
|
3,5 mA
|
|
4 mA
|
0,5 ms
|
0,5 ms
|
190 V
|
250 V
|
170 V
|
120 V
|
63 kΩ
|
220
|
1,8 A
|
1 mA
|
12 A (10 ms) A
|
250 V
|
1 V
|
-25 °C
|
|
Select a variant in the list