Important notice - We will be performing system maintenance from 4pm Friday 19th April. Whilst we are performing this maintenance there will be no pricing available or ability to place orders. This will last for 2-3 days. Please contact customer support for any enquiries 0116 284 9900. We apologise for any inconvenience caused.
PULS
The Puls Dimension DC-DC converter features high efficiency, very compact dimensions and mounting on DIN rail. The input voltage can come from, for example, a power supply unit, batteries or solar panels. The output is galvanically isolated from the input. Examples of fields application are installation at the end of a long cable to stabilize voltage, conversion of one voltage to another or for isolation of specific loads. The DC-DC converters are equipped with a soft-start function, entailing that the current gradually rises to the nominal value. In this way, high starting currents are avoided that can cause voltage drops on the primary side and produce start-up problems. A 20 % power boost provides additional power resources during temporary current peaks. Article CD5.241-S1 is equipped with status outputs for controlling both the output voltage and the input voltage.
Â
We recommend free space of 40 mm above the unit, 20 mm under and 5 mm at the sides.
Â
Input data |
|
---|---|
Input voltage dc | 24 V |
Input voltage dc min | 18 V DC |
Input voltage dc max | 32,4 V DC |
Input capacitance | 3000 µF |
Inrush current | Typ. 1,2 A @ 24 V DC |
Max entrance tripple | 5 V pp |
Output data |
|
Output voltage | 24 V DC |
Output voltage min | 24 V DC |
Output voltage max | 28 V DC |
Output current | 5 A |
Power | 120 W |
Efficiency / Lifetime / MTBF |
|
Efficiency | 90,3 % |
Life span | 65000 h @ 24 V DC, 5 A, 40 °C |
MTBF (IEC 61709) | 1178000 @ 24 V DC, 5 A, 40 °C |
Dimensions |
|
Width | 32 mm |
Height | 124 mm |
*Invisible Heading* |
|
---|---|
Depth | 102 mm |
Weight | 0,425 kg |
Other |
|
Approvals | ABS, ATEX, CB, CE, CSA, GL, IECEx, UL |
Keep time | Typ. 6 ms @ 24 V DC |
IP class | IP20 |
Clamp type | Screw on |
Material protection | Aluminium |
Ripple max | 50 mV pp |
Series | Dimension C |
Power drop from +60 °C to + 70 °C | 3 W/°C |
Temperature min without derating | -25 °C |
Temperature max without derating | 60 °C |
Startup delay | 650 ms |
Type Power Supply | DC-DC |
The Puls Dimension DC-DC converter features high efficiency, very compact dimensions and mounting on DIN rail. The input voltage can come from, for example, a power supply unit, batteries or solar panels. The output is galvanically isolated from the input. Examples of fields application are installation at the end of a long cable to stabilize voltage, conversion of one voltage to another or for isolation of specific loads. The DC-DC converters are equipped with a soft-start function, entailing that the current gradually rises to the nominal value. In this way, high starting currents are avoided that can cause voltage drops on the primary side and produce start-up problems. A 20 % power boost provides additional power resources during temporary current peaks. Article CD5.241-S1 is equipped with status outputs for controlling both the output voltage and the input voltage.
Â
We recommend free space of 40 mm above the unit, 20 mm under and 5 mm at the sides.
Â
Renowned for high-quality cable cutting and crimping tools, Klauke serves electrical contractors, cable jointers, and linemen across a spectrum of sectors
At OEM Automatic, we can supply a series of components for your one project. All under one roof. This case study discusses how we supplied several components for our customer's new electro-pneumatic control box.Â
To promote constant and reliable performance, as well as a longer life of parts in the vehicle, it is important to consider the right cable protector.
We have now added switch disconnectors to our range! Switch disconnectors contribute to the overall functionality and safety of electrical systems.
LOCC-Box from Lutze is an intelligent current monitoring device that provides reliable protection of DC circuits in a slimline 8.1mm housing.
OEM Automatic has integrated push-in technology into it's product offering for many years now. In this blog post, we'll explore the various benefits of push-in technology and some of the products we offer that make use of this innovation, such as push-in terminals, push-in sockets, and even push-in heaters.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Input voltage dc min | Output voltage | Output voltage min | Output voltage max | Output current | Power | Efficiency | Life span | MTBF (IEC 61709) | Weight | Approvals | Keep time | Clamp type | Ripple max | Status output | Power drop from +60 °C to + 70 °C | Temperature max without derating | Startup delay | DC relay output | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
PSU 24V dc I/P 12V dc 8A 96W O/P
Art:
CD5.121
Copied
|
18 V DC
|
12 V DC
|
12 V DC
|
15 V DC
|
8 A
|
96 W
|
88,2 %
|
63000 h @ 12 V DC, 8 A, 40 °C
|
1161000 @ 12 V DC, 8 A, 40 °C
|
0,425 kg
|
ABS, ATEX, CB, CE, CSA, GL, IECEx, UL
|
Typ. 7 ms @ 24 V DC
|
Screw on
|
75 mV pp
|
|
2,5 W/°C
|
60 °C
|
420 ms
|
|
| ||
PSU 24V dc I/P 24V dc 5A 120W O/P
Art:
CD5.241
Copied
|
18 V DC
|
24 V DC
|
24 V DC
|
28 V DC
|
5 A
|
120 W
|
90,3 %
|
65000 h @ 24 V DC, 5 A, 40 °C
|
1178000 @ 24 V DC, 5 A, 40 °C
|
0,425 kg
|
ABS, ATEX, CB, CE, CSA, GL, IECEx, UL
|
Typ. 6 ms @ 24 V DC
|
Screw on
|
50 mV pp
|
|
3 W/°C
|
60 °C
|
650 ms
|
|
| ||
PSU 24V dc I/P 24V dc 3.8A 92W O/P NEC-CLASS-2
Art:
CD5.241-L1
Copied
|
14,4 V DC
|
24 V DC
|
24 V DC
|
24,1 V DC
|
3,8 A
|
92 W
|
90,5 %
|
134000 h @ 24 V DC, 3,8 A, 40 °C
|
1487000 h @ 24 V DC, 3,8 A, 40 °C
|
0,425 kg
|
ABS, ATEX, CB, CE, CSA, GL, IECEx, NEC Class 2, UL
|
Typ. 7 ms @ 24 V DC
|
Spring-clamp
|
50 mV pp
|
|
0 W/°C
|
70 °C
|
290 ms
|
|
| ||
PSU 24V dc I/P 24V dc 5A 120W O/P DC-OK Input-Low contacts
Art:
CD5.241-S1
Copied
|
18 V DC
|
24 V DC
|
24 V DC
|
28 V DC
|
5 A
|
120 W
|
90,2 %
|
60000 h @ 24 V DC, 5 A, 40 °C
|
1048000 @ 24 V DC, 5 A, 40 °C
|
0,45 kg
|
ABS, ATEX, CB, CE, CSA, GL, IECEx, UL
|
Typ. 6 ms @ 24 V DC
|
Spring-clamp
|
50 mV pp
|
DC-OK and Input-Low
|
3 W/°C
|
60 °C
|
650 ms
|
Yes
|
|