• black icon of a bullhorn 30 years industry experience
  • black icon of three cubes Over 8,000 products in stock
  • Black icon of a clock Order by 16:00 and receive the next working day
PULS
PULS

Power supply 1-phase, 24 V dc Miniline 2 Series

  • Output current 2.5 A
  • Up to 90.4% efficiency
  • Working temp. -40 to +60°C
  • ac and dc input voltage

Product description

A compact size, light weight, simple mounting onto the DIN-rail and the utilization of only quality components are what makes the MiniLine power supplies so easy to use and install within seconds.

A rugged electrical and mechanical design as well as a high immunity against electrical disturbances on the mains provides reliable output power. This offers superior protection for equipment which is connected to the public mains network or is exposed to a critical industrial environment.

The specialty of the ML60.242 is the electronic inrush current limitation and the suitability for very low ambient temperatures. The unit is fully specified down to -40°C.

The supplementary MiniLine decoupling diode module MLY10.241 allows building of redundant systems or to protect against back-feeding voltages.

 

Operating temperature is the same as the ambient temperature and the air temperature is defined as 2 cm below the unit.

 

Output power vs ambient temperature

Output power vs ambient temperature

Operating temperature is the same as the ambient temperature
and the air temperature is defined as 2 cm below the unit.

 

 

Output characteristic

Output characteristics

 

 

 

 

 

Parts Price

Part

ML60.242
PSU 100-240V ac I/P 24V dc 2.5A 60W O/P -40°C

Technical data

Input data

Input voltage ac 100-240 V
Input voltage ac min 85 V AC
Input voltage ac max 264 V AC
Input voltage dc 110-300 V
Input voltage dc min 88 V DC
Input voltage dc max 375 V DC
Inrush current at 120 V ac typical 6 A
Inrush current at 230 V ac typical 6 A
Input voltage range Wide-range
Power factor at 120 V ac, full load. Typical 0,54
Power factor at 230 V ac, full load. Typical 0,44
Number of phases 1

Output data

Output voltage 24 V DC
Output voltage min 24 V DC
Output voltage max 28 V DC
Output current 2,5 A
Power 60 W

Efficiency / Lifetime / MTBF

Efficiency at 120 V ac, full load, typical 88,5 %
Efficiency at 230 V ac, full load, typical 90,4 %
Lifetime at 120 V ac, full load and +40 ° C 66000 h
Lifetime at 230 V ac, full load and +40 ° C 90000 h
MTBF (IEC 61709) 230 V ac, max load, 40 ° C 1866000 h

Dimensions

Width 45 mm
Height 75 mm
Depth 91 mm
Weight 0,25 kg

Other

Approvals ABS, CB, CE, CSA, EAC, GL, NEC Class 2, UL
Hold time at 120 V ac, typical full load 24 ms
Hold time at 230 V ac, typical full load 107 ms
IP class IP20
Clamp type Screw on
Material protection ABS plastic
Supply frequency 50-60 ±6 %
Ripple max 50 mV pp
Series Miniline
Power consumption 120 V ac 1,05 A
Power consumption 230 V ac 0,66 A
Power drop from +60 °C to + 70 °C 1,5 W/°C
Temperature min without derating -40 °C
Temperature max without derating 60 °C
Type Power Supply AC-DC

Measurements and connections

Technical illustrations

  • For good cooling free space of 40 mm above and 20 mm under the power supply is recommended. The sides 0 mm unless neighbouring products are a heat source, for example, a power supply unit. Leave then a 15 mm air gap.

    For good cooling free space of 40 mm above and 20 mm under the power supply is recommended. The sides 0 mm unless neighbouring products are a heat source, for example, a power supply unit. Leave then a 15 mm air gap.

  • For good cooling free space of 40 mm above and 20 mm under the power supply is recommended. The sides 0 mm unless neighbouring products are a heat source, for example, a power supply unit. Leave then a 15 mm air gap.

    For good cooling free space of 40 mm above and 20 mm under the power supply is recommended. The sides 0 mm unless neighbouring products are a heat source, for example, a power supply unit. Leave then a 15 mm air gap.

  • Operating temperature is the same as the ambient temperature and the air temperature is defined as 2 cm below the unit.

    Operating temperature is the same as the ambient temperature and the air temperature is defined as 2 cm below the unit.

Resource

Contact us

If you need any help, you can contact us in one of the following ways:

0116 284 9900

Send an e-mail

Use live chat