1-Phase power network digital panel meter for measurement of a.c. voltage, a.c. current, active, reactive and apparent power, cos φ, tg φ, φ, frequency, active and reactive and apparent energy.
Single phase AC current / voltage input
Wide voltage, AC/DC control
5 Digit, 3 Colour, Programmable display
Product description
Inputs
Input kind
Measuring range
Min...max signal value
Ratio values
Voltage input
0...100 V or 0...400 V
0.05...1.2 Un
0.1...4000.0
Current input
0...1 A or 0...5 A
0.005...1.2 In
1...10000
Measuring ranges
Measured value
Indication range
Measuring range
Basic error
Current 1 A/5 A
0.000...60 kA
0.02...6 A a.c.
± 0.2%
Voltage 100 V/400 V
0.0...192 MV
1...480 V a.c.
± 0.2%
Frequency
45.00...100.00 Hz
45.00...66.00...100.00 Hz
± 0.2%
Active power
-19999...99999 MW
-2.88 kW...1.40 W...2.88 kW
± 0.5%
Reactive power
-19999...99999 Mvar
-2.88 kvar...1.40 var...2.88 kvar
± 0.5%
Apparent power
0.00...99999 MVA
1.40 VA...2.88 kVA
± 0.5%
Cofficient PF
-1...1
-1...0...1
± 0.5%
Tangens φ
-1.2...1.2
-1.2...0...1.2
± 1%
φ
0...359
0...359
± 1%
Active energy
0...9 999 999.9 kWh
0...9 999 999.9 kWh
± 0.5%
Reactive energy
0...9 999 999.9 kVarh
0...9 999 999.9 kVarh
± 0.5%
Apparent energy
0...9 999 999.9 kVA
0...9 999 999.9 kVA
± 0.5%
Current time
0.00...23.59
0.00..23.59
1 sec/ 24 h
Outputs
Output kind
Properties
Remarks
Relay output
• 2 x relays, voltageless NO contacts, load-carrying capacity 250 V a.c./ 0.5 A a.c. • 2 x relays, voltageless CO contacts, load-carrying capacity 250 V a.c./ 0.5 A a.c.
2 x contacts optional
Analog output
• current programmable 0/4...20 mA, load resistance ≤ 500 Ω • voltage programmable 0...10 V, load resistance ≥ 500 Ω • resolution 0.01 % of the range
optional resolution 0.01% of the range
Energy pulse output
• OC type, passive; supply: voltage 18...27 V, current 10...27 mA; A class acc. to EN 62053-31 • Output pulse constant: 5000 imp./kWh, independently of Ku and Ki settings
Digital interface
Interface type
Transmission protocol
Modes
Baud rates
RS-485
MODBUS RTU
8N2, 8E1, 8O1, 8N1
4.8, 9.6, 19.2, 38.4 kbit/s
External features
Readout field
5 digit LED display , indication range -19999..99999 digit, height: 14 mm
Thank you for requesting a quote. We will e-mail you as soon as possible.
Something went wrong. No offer request has been sent.
Successfully added batches to cart!
Failed to add to cart. Please contact customer support for help.
Number of variants matching filter 6/6 |
Part numbers
Parts
Price
Outputs
Supply voltage
N30P10XX
Panel Meter, 2x OC Outputs, 85-253V ac
2 relays (NO)
85-253V ac/dc
N30P11XX
Panel Meter, 2 x OC Outputs, RS-485, 1A Ouput 85-253V ac
analog, RS485, 2 relays
85-253V ac/dc
N30P12XX
Panel Meter, 4 x OC Outputs, RS-485, 1A Ouput, 85-253V ac
analog,RS485, 4 relays
85-253V ac/dc
N30P20XX
Panel Meter, 2x OC Outputs, 20-60V dc
2 relays (NO)
20-40V ac/dc
N30P21XX
Panel Meter, 2 x OC Outputs, RS-485, 1A Ouput 20-60V dc
analog, RS485, 2 relays
20-40V ac/dc
N30P22XX
Panel Meter, 4 x OC Outputs, RS-485, 1A Ouput, 20-60V dc
analog,RS485, 4 relays
20-40V ac/dc
Part
N30P10XX
Panel Meter, 2x OC Outputs, 85-253V ac
Technical data
Additional functions
Conversion of any measured value into current or voltage analog signal. Storage of minimal and maximal values for all measured quantites. 21-point rescaling for the measured value (does not apply to N30P and N27P). Password protection. Programmable current and voltage transformer ratio (applies to N27P and N30P).
Cookies help us improve your experience with us, so in order to be able to handle login information, offer you personalised content and for basic functionality of this website, we use some cookies.
We will never sell on any information about you.
You can accept all cookies or personalise your cookies preferences, you can also change your cookie preferences at any time by visiting our contact page.
Necessary Cookies
These cookies are necessary for the website to work and can not be turned off in our systems. They are usually used only in response to actions you have taken in connection with a service request, for example when setting personal preferences, logging in or filling out a form.
Analysis and measurement cookies
These cookies allow us to count the number of visits and traffic sources so that we can measure and improve our website performance. They help us know which pages are more or less popular and how visitors navigate around the site. The information that these cookies collect is aggregated and therefore completely anonymous. If you do not allow these cookies, we do not know when you have visited our website.
Marketing cookies
These cookies can be added by our partners. They can use them to create a profile of you, based on your interests, to show you more relevant information. They do not store any personal information - only information about your browser and device. If you do not accept these cookies, you will have a more general and less customized user experience.