• black icon of a bullhorn 30 years industry experience
  • black icon of three cubes Over 8,000 products in stock
  • Black icon of a clock Order by 16:00 and receive the next working day
CROUZET CONTROL
CROUZET CONTROL

1 Phase Over/Under Current Relay MIC

  • Measurement range 2-20 A ac
  • Integrated current transformer
  • Over/under-current function
  • Measures true RMS

Product description

For control of over-current in ac networks via internal current transformer. The unit requires supply voltage. The current conductor is run through the hole in the relay (current transformer) for measurement of the ac current. The current transformer hole is 10 mm. The MIC relay controls over-currents. The relay activates (closes) when the current exceeds the limit value that is shown on the front and drops out (opens) when the current drops below the limit value, minus the hysteresis value (static 15 % of the displayed limit value). When Y1 is connected to A1 (+), the relay function is inverted. The relay drops out when the current exceeds the limit value shown on the front and activates when the current drops below the hysteresis value (over-current). The relay can also be used for under-current function. Contact OEM Automatic's Panel Components product area about this function.

 

Parts Price

Part

Crouzet current monitoring relay

84871122
Current Monitor Relay MIC 24-240V ac/dc

Technical data

Approvals CE, CSA, GL, RoHS, UL
Breaking capacity 5A, 250V AC/DC
Current transformer diameter 10 mm
Function Over/Undercurrent
Lower limit 2A
Output Relay 1 pole C/O
Overload continuous max 100 A
Recovery time min 0,2 ms
Storage temperature max 70 °C
Storage temperature min -40 °C
Supply voltage 24-240V AC/DC
Temperature operational max 50 °C
Temperature operational min -20 °C
Time delay startup 0,5 s
Upper limit 20A
Weight 110 g

Measurements and connections

Technical illustrations

  • F1: Fast-blow fuse 100 mA (recommendation)

    F1: Fast-blow fuse 100 mA (recommendation)

  • MIC over-current<br />1: Limit value<br />2: Hysteresis<br />3: Closing upon exceeding limit value (Y1 and A1 not strapped)<br />4: Opening upon exceeding limit value (Y1 and A1 strapped)<br />5: Connection of operating voltage<br />6: Monitored current

    MIC over-current
    1: Limit value
    2: Hysteresis
    3: Closing upon exceeding limit value (Y1 and A1 not strapped)
    4: Opening upon exceeding limit value (Y1 and A1 strapped)
    5: Connection of operating voltage
    6: Monitored current