STEGO
This mechanical hygrostat KFR 012 is preset at 65 % or 50 %. This makes it easier to install hygrostats. It can often be difficult to know which humidity is to be set on the hygrostat. If the hygrostat is set at a value that is too low, the heating fan runs too frequently and thus produces large energy losses, or if the hygrostat is set at a value that is too high, components in the cabinet can be damaged. For the sake of simplicity, STEGO has developed two different models.
65 % humidity (rF) – for most cabinets with normal humidity
50 % humidity (rF) – for cabinets with components that are sensitive to high humidity.
General data |
|
|---|---|
| Control range humidity from | 50 % RF |
| Control range humidity to | 50 % RF |
| Hysteresis humidity | 4% RH |
| Mounting | Clip on, DIN rail |
| Contact type | 1 x N/O |
| Colour | Light grey |
Rated operating conditions |
|
| Breaking capacity | 250VAC, 5 (0.2) A |
| Contact resistance | <10 mΩ |
| Connection type | 2-pole terminal for 2.5mm² |
| Operational temperature | 0 °C ... +60°C |
| Storage temperature | -20°C ... +80°C |
*Invisible Heading* |
|
|---|---|
| Life span | > 50,000 cycles |
| Humidity storage | <90% RH |
Dimensions |
|
| Height | 60 mm |
| Depth | 33 mm |
| Weight | 0.04 kg |
| Material of body | Plastic |
Safety & approvals |
|
| IP class | IP20 |
| Approvals | CE, UL, VDE |
| Flammability class | UL94-V0 |
| EMC | EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 |
This mechanical hygrostat KFR 012 is preset at 65 % or 50 %. This makes it easier to install hygrostats. It can often be difficult to know which humidity is to be set on the hygrostat. If the hygrostat is set at a value that is too low, the heating fan runs too frequently and thus produces large energy losses, or if the hygrostat is set at a value that is too high, components in the cabinet can be damaged. For the sake of simplicity, STEGO has developed two different models.
65 % humidity (rF) – for most cabinets with normal humidity
50 % humidity (rF) – for cabinets with components that are sensitive to high humidity.
|
|
|
|
|
|
||
|---|---|---|---|---|---|---|
|
|
|
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
| Parts | Control range humidity from | Control range humidity to | Price | ||
|---|---|---|---|---|---|
|
KFR 012 Hygrostat, Preset 50% RH, normally open
Art:
01241.0-00
Copied
|
50 % RF
|
50 % RF
|
| ||
|
KFR 012 Hygrostat, Preset 65% RH, normally open
Art:
01240.0-00
Copied
|
65 % RF
|
65 % RF
|
|
Select a variant in the list