TEKNOMEGA

SOLID ALUMINIUM BARS

BAP

Teknomega have created a free to download software for calculating and selecting the most suitable busbar for your application. Find out more here.

 

Solid aluminium bars use Aluminium type EN-AW 1350 A and have the following technical properties; a tensile strength of 250N/mm2, a resistivity of 0.0172Ωmm2/m, and a density of 8.9kg/dm3.

Aluminium busbar for power distribution gives an economic advantage compared to copper bars due to the lower cost of aluminium and to a significant difference in the weight / volume.

 

Aluminium bars weigh up to 70% less than copper bars, compared with a reduction in electrical capacity of only about 30%.

 

The use of aluminium bars for carrying electrical current is therefore recommended in switchboards, distribution equipment and systems where there are no space problems, or where weight reduction is critical.

 

Read more
  • Thickness 10 mm.
  • Length 2000 and 4000 mm
  • Significant cost saving
  • Weight saving up to 70%
Teknomega SOLID ALUMINIUM BARS BAP

Eplan Logo, data portal for 3D drawings

To view Teknomega Products via ePlan see the link under 'downloadable resources' further down the page

Selected variant

Selected variant

Technical data

General Data

Cross section 200 mm²
Current at ΔT 50°C 434 A

Dimensions

Length 2000 mm
Thickness 10 mm
Width 20 mm

Ampacity

Current at ΔT 30°C 331 A

Additional Data

Pack size 2
Weight 0,54 kg

Product description

Teknomega have created a free to download software for calculating and selecting the most suitable busbar for your application. Find out more here.

 

Solid aluminium bars use Aluminium type EN-AW 1350 A and have the following technical properties; a tensile strength of 250N/mm2, a resistivity of 0.0172Ωmm2/m, and a density of 8.9kg/dm3.

Aluminium busbar for power distribution gives an economic advantage compared to copper bars due to the lower cost of aluminium and to a significant difference in the weight / volume.

 

Aluminium bars weigh up to 70% less than copper bars, compared with a reduction in electrical capacity of only about 30%.

 

The use of aluminium bars for carrying electrical current is therefore recommended in switchboards, distribution equipment and systems where there are no space problems, or where weight reduction is critical.

 

Accessories

Related

Parts Cross section Current at ΔT 50°C Length Width Current at ΔT 30°C Pack size Weight Price
200 mm²
434 A
2000 mm
20 mm
331 A
2
0,54 kg
300 mm²
583 A
2000 mm
30 mm
445 A
2
0,81 kg
400 mm²
730 A
2000 mm
40 mm
557 A
2
1,08 kg
500 mm²
874 A
2000 mm
50 mm
667 A
2
1,35 kg
600 mm²
1006 A
2000 mm
60 mm
774 A
2
1,62 kg
800 mm²
1278 A
2000 mm
80 mm
983 A
2
2,16 kg
1000 mm²
1547 A
2000 mm
100 mm
1190 A
2
2,7 kg
1200 mm²
1807 A
2000 mm
120 mm
1390 A
2
3,24 kg
200 mm²
434 A
4000 mm
20 mm
331 A
1
0,54 kg
300 mm²
583 A
4000 mm
30 mm
445 A
1
0,81 kg
400 mm²
730 A
4000 mm
40 mm
557 A
1
1,08 kg
500 mm²
874 A
4000 mm
50 mm
667 A
1
1,35 kg
600 mm²
1006 A
4000 mm
60 mm
774 A
1
1,62 kg
800 mm²
1278 A
4000 mm
80 mm
983 A
1
2,16 kg
1000 mm²
1547 A
4000 mm
100 mm
1190 A
1
2,7 kg
1200 mm²
1807 A
4000 mm
120 mm
1390 A
1
3,24 kg

Selected variant

Select a variant in the list

Contact us

If you need any help, you can contact us in one of the following ways:

phone 0116 284 9900

Send an e-mail Send an e-mail

comments Use live chat