1 phase over/under current relay HIL, HIH

  • Two models: HIL 2 mA-500 mA, HIH 0.1 A-10 A
  • Galvanic isolation control/measurement
  • Automatic detection of ac or dc
  • 35 mm cabinet with DIN rail

Product description

HIL and HIH control relays are used for monitoring 1-phase AC/DC currents. The relay automatically detects the form of current that is to be measured. The relay requires a supply voltage. Using a rotary switch, selection can be made between over- or under-current, with or without memory.If “with memory” is selected, the supply voltage to the relay must be switched off to restart. The switch position and consequently the control relay's function mode is detected when the operating voltage is switched on. If the switch is in the wrong position, the relay will remain deactivated and the LEDs will flash to indicate incorrect setting. If the switch position is changed during operation, all LEDs begin to flash but the unit will continue to function normally with the function that was set at the most recent power connection. The LEDs return to normal function when the switch has been returned to its original position, which was set before the first power connection. The limit value for over- and under-current is set with a potentiometer that is scaled in the percentage of the current range that is to be monitored. The hysteresis value is similarly set with a scale from 5-50 % of the set limit value. The hysteresis value cannot exceed the measurement range's limit value. Both relays are equipped with a time delay (Tt) to ignore temporary current deviations. HIL and HIH also have a time delay upon start-up (Tt), adjustable between 1-20 s to avoid current peaks or current dips upon start-up. If the current should exceed 10 A, a current transformer can be used. Green LED (Un) indicates supply voltage OK. Yellow LED (R) indicates active relay output.

 

Part numbers

Parts Price E1-M max. continuous current in 25°C E1-M max. current <1s at 25°C E2-M max. continuous current in 25°C E2-M max. current <1s at 25°C E3-M max. continuous current in 25°C E3-M max. current <1s at 25°C Measurement range E1-M Measurement range E2-M Measurement range E3-M
2 A 17 A 11 A 20 A 11 A 50 A 0,1-1A 0,5-5A 1-10A
0,4 A 1 A 1 A 5 A 2 A 8 A 2-20mA 10-100mA 50-500mA

Part

Control relay

84871130
Current Monitor Relay HIH 24-240V ac/dc

Technical data

Adjustable limit value from 10 %
Adjustable limit value to 100 %
Approvals CE, CSA, RoHS, UL
Breaking capacity 5A, 250V AC/DC
E1-M max. continuous current in 25°C 2 A
E1-M max. current <1s at 25°C 17 A
E2-M max. continuous current in 25°C 11 A
E2-M max. current <1s at 25°C 20 A
E3-M max. continuous current in 25°C 11 A
E3-M max. current <1s at 25°C 50 A
Function Over/Undercurrent
IP class connection IP20
IP class housing IP30
Measurement range E1-M 0,1-1A
Measurement range E2-M 0,5-5A
Measurement range E3-M 1-10A
Mounting DIN rail
Output Relay 2 pole C/O
Storage temperature max 70 °C
Storage temperature min -30 °C
Supply voltage 24-240V ac/dc
Temperature operational max 50 °C
Temperature operational min -20 °C
Time delay startup 1-20s
Time delay when exceeding the limit value 0,1-3s
Weight 130 g

Measurements and connections

Technical illustrations

  • F1: Fast-blow fuse 1 A (recommendation) <br />NB: When monitoring dc from the same power supply that is connected at <br />A1 or A2, the connection point M must be connected directly to minus (-) in this power supply.

    F1: Fast-blow fuse 1 A (recommendation)
    NB: When monitoring dc from the same power supply that is connected at
    A1 or A2, the connection point M must be connected directly to minus (-) in this power supply.

  • With memory<br />1: Limit value<br />2: Hysteresis<br />3: Over-current<br />4: Under-current<br />5: Activation of operating voltage<br />6: Monitored current<br />7: Time delay, start-up (Ti)<br />8: Time delay upon exceeding limit value (Tt)

    With memory
    1: Limit value
    2: Hysteresis
    3: Over-current
    4: Under-current
    5: Activation of operating voltage
    6: Monitored current
    7: Time delay, start-up (Ti)
    8: Time delay upon exceeding limit value (Tt)

  • Without memory<br />1: Limit value<br />2: Hysteresis<br />3: Over-current<br />4: Under-current<br />5: Activation of operating voltage<br />6: Monitored current<br />7: Time delay, start-up (Ti)<br />8: Time delay upon exceeding limit value (Tt)

    Without memory
    1: Limit value
    2: Hysteresis
    3: Over-current
    4: Under-current
    5: Activation of operating voltage
    6: Monitored current
    7: Time delay, start-up (Ti)
    8: Time delay upon exceeding limit value (Tt)