• black icon of a bullhorn 30 years industry experience
  • black icon of three cubes Over 8,000 products in stock
  • Black icon of a clock Order by 16:00 and receive the next working day
CONTA-CLIP
CONTA-CLIP

Installation terminals - FRKI

FRKI

  • Compact
  • Quick & easy installation
  • Polyamide 6.6-V0

Product description

The FNT neutral disconnect terminals feature an integral mounting post for attaching the 10x3-mm neutral busbar.

No additional plates or fixings are required,  as a secure contact to the busbar is made using the

no-screw slider for the neutral conductor.

With the FSLI protective earth terminals, the PE potential is connected via the PE foot (which contacts the DIN rail on both sides).

Solid wires and flexible wires with wire-end ferrules can be inserted into the connection mechanism without the need for tools.

The pressure spring opens automatically when the wire is inserted; this ensures a secure contact with the busbar.

A standard screwdriver can be used to open the clamp for release and for the insertion of stranded wire without ferrules.

This range can also be combined with the FDLIS three-level installation terminal range.

The one-level terminals – FRKI, FSLI, and FNT – can be used in combination with the three-level FDLIS installation terminals, as the height of the neutral busbar is identical in both versions.

Where the neutral busbar is not being used with the 16mm terminals, there is the FRK16 in the standard range, this has a central din rail mounting foot and provides a symmetrical layout.

 

Part numbers

Parts Price Rated wire cross section Colour Rated voltage IEC Rated current IEC Rated impulse voltage Approvals Length Width Height TS 35/7.5 Height Connections Plug gauge acc. EN 60 947-1 Cross connect channels Cross section single wire from Cross section single wire to Cross section stranded wire from Cross section stranded wire to Cross section stranded with ferrule from Cross section stranded with ferrule to Rated wire cross section from (AWG) Rated wire cross section to (AWG) Stripping length Rated voltage UL Rated current UL UL test standard Rated voltage CSA Rated current CSA CSA test standard Rated voltage CSAus Rated current CSAus CSAus test standard Rated voltage cUL Rated current cUL cUL test standard EAC test standard KEMA KEUR test standard Country of origin Weight Pack size
4 mm² Beige 800 V 32 A 8 kV CSA, CSA US, KEMA KUR, EAC 52,5 mm 5,1 mm 38,5 mm 37,5 mm 2 A4 2 0,5 mm² 6 mm² 0,6 mm² 6 mm² 0,5 mm² 4 mm² 20 10 12 mm 600 V 28 A C22.2 No 158 600 V 28 A UL 1059 TR ZU 004/2011 EN 60947-7-1:2009 BG 8,25 g 100
4 mm² Blue 800 V 32 A 8 kV CSA, CSA US, KEMA KUR, EAC 52,5 mm 5,1 mm 38,5 mm 37,5 mm 2 A4 2 0,5 mm² 6 mm² 0,6 mm² 6 mm² 0,5 mm² 4 mm² 20 10 12 mm 600 V 28 A C22.2 No 158 600 V 28 A UL 1059 TR ZU 004/2011 EN 60947-7-1:2009 BG 8,25 g 100
4 mm² Orange 800 V 32 A 8 kV CSA, CSA US, KEMA KUR, EAC 52,5 mm 5,1 mm 38,5 mm 37,5 mm 2 A4 2 0,5 mm² 6 mm² 0,6 mm² 6 mm² 0,5 mm² 4 mm² 20 10 12 mm 600 V 28 A C22.2 No 158 600 V 28 A UL 1059 TR ZU 004/2011 EN 60947-7-1:2009 BG 8,25 g 100
4 mm² Green/yellow CSA, CSA US, KEMA KUR, EAC 52,5 mm 5,1 mm 38,5 mm 37,5 mm 2 A4 1 0,5 mm² 6 mm² 0,6 mm² 6 mm² 0,5 mm² 4 mm² 20 10 12 mm C22.2 No 158 UL 1059 TR ZU 004/2011 EN 60947-7-2:2009 BG 11,25 g 100
4 mm² Blue 250 V 32 A 8 kV KEMA KUR 64 mm 5,1 mm 42,5 mm 41,5 mm 1 A4 1 0,5 mm² 6 mm² 0,6 mm² 6 mm² 0,5 mm² 4 mm² 20 10 12 mm EN 60947-7-1:2009 BG 9,25 g 100
10 mm² Beige 800 V 57 A 8 kV CSA, CSA US, KEMA KUR, EAC 56,5 mm 8,1 mm 40,5 mm 39,8 mm 2 A5 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 22 10 12 mm 600 V 44 A C22.2 No 158 600 V 44 A UL 1059 TR ZU 004/2011 EN 60947-7-1:2009 BG 14,25 g 100
10 mm² Blue 800 V 57 A 8 kV CSA, CSA US, KEMA KUR, EAC 56,5 mm 8,1 mm 40,5 mm 39,8 mm 2 A5 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 22 10 12 mm 600 V 44 A C22.2 No 158 600 V 44 A UL 1059 TR ZU 004/2011 EN 60947-7-1:2009 BG 14,25 g 100
10 mm² Orange 800 V 57 A 8 kV CSA, CSA US, KEMA KUR, EAC 56,5 mm 8,1 mm 40,5 mm 39,8 mm 2 A5 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 22 10 12 mm 600 V 44 A C22.2 No 158 600 V 44 A UL 1059 TR ZU 004/2011 EN 60947-7-1:2009 BG 14,25 g 100
10 mm² Red 800 V 57 A 8 kV CSA, CSA US, KEMA KUR, EAC 56,5 mm 8,1 mm 40,5 mm 39,8 mm 2 A5 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 22 10 12 mm 600 V 44 A C22.2 No 158 600 V 44 A UL 1059 TR ZU 004/2011 EN 60947-7-1:2009 CZ 14,25 g 100
10 mm² Green/yellow CSA, CSA US, KEMA KUR, EAC 56,5 mm 8,1 mm 40,5 mm 39,8 mm 2 A5 1 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 22 10 12 mm C22.2 No 158 UL 1059 TR ZU 004/2011 EN 60947-7-2:2009 BG 20,25 g 100
10 mm² Blue 250 V 57 A 8 kV KEMA KUR 67,5 mm 8,1 mm 40,5 mm 39,8 mm 1 A5 1 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 22 10 12 mm EN 60947-7-1:2009 BG 16,25 g 100
10 mm² Beige 800 V 57 A 8 kV EAC 82,4 mm 8,1 mm 39,8 mm 3 A3 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 16 8 12 mm 600 V 44 A UL 1059 44 V 600 A C22.2 No 158 TR ZU 004/2011 EN 60947-7-1:2009 BG 27,09 g 50
10 mm² Blue 800 V 57 A 8 kV EAC 82,4 mm 8,1 mm 39,8 mm 3 A3 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 16 8 12 mm 600 V 44 A UL 1059 44 V 600 A C22.2 No 158 TR ZU 004/2011 EN 60947-7-1:2009 BG 27,09 g 50
10 mm² Orange 800 V 57 A 8 kV EAC 82,4 mm 8,1 mm 39,8 mm 3 A3 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 16 8 12 mm 600 V 44 A UL 1059 44 V 600 A C22.2 No 158 TR ZU 004/2011 EN 60947-7-1:2009 BG 27,09 g 50
10 mm² Green/yellow EAC 82,4 mm 8,1 mm 39,8 mm 3 A3 2 1,5 mm² 10 mm² 1,5 mm² 10 mm² 1,5 mm² 10 mm² 16 8 12 mm UL 1059 C22.2 No 158 TR ZU 004/2011 EN 60947-7-2:2009 BG 33,87 g 50
16 mm² Beige 1000 V 76 A 8 kV EAC 72,4 mm 12,1 mm 49 mm 48 mm 2 A7 2 2,5 mm² 25 mm² 2,5 mm² 25 mm² 2,5 mm² 16 mm² 14 4 18 mm 600 V 75 A UL 1059 75 V 600 A C22.2 No 158 TR ZU 004/2011 EN 60947-7-1:2009 CZ 17,8 g 50
16 mm² Blue 1000 V 76 A 8 kV EAC 72,4 mm 12,1 mm 49 mm 48 mm 2 A7 2 2,5 mm² 25 mm² 2,5 mm² 25 mm² 2,5 mm² 16 mm² 14 4 18 mm 600 V 75 A UL 1059 75 V 600 A C22.2 No 158 TR ZU 004/2011 EN 60947-7-1:2009 CZ 17,8 g 50
16 mm² Orange 1000 V 76 A 8 kV EAC 72,4 mm 12,1 mm 49 mm 48 mm 2 A7 2 2,5 mm² 25 mm² 2,5 mm² 25 mm² 2,5 mm² 16 mm² 14 4 18 mm 600 V 75 A UL 1059 75 V 600 A C22.2 No 158 TR ZU 004/2011 EN 60947-7-1:2009 CZ 17,8 g 50
16 mm² Green/yellow EAC 72,4 mm 12,1 mm 49 mm 48 mm 2 A7 1 2,5 mm² 25 mm² 2,5 mm² 25 mm² 2,5 mm² 16 mm² 14 4 18 mm UL 1059 C22.2 No 158 TR ZU 004/2011 EN 60947-7-2:2009 CZ 44,7 g 50

Part

3276.2
FRKI 2.5-4 Beige, 4mm² Installation feed through, push-in

Technical data

General data

Rated wire cross section 4 mm²
Colour Beige
Rated voltage IEC 800 V
Rated current IEC 32 A
Mounting TS 35
Rated impulse voltage 8 kV
Overvoltage category III
Contamination degree 3
Approvals CSA, CSA US, KEMA KUR, EAC

Dimensions

Length 52,5 mm
Width 5,1 mm
Height TS 35/7.5 38,5 mm
Height 37,5 mm

Connection data

Connections 2
Number of levels 1
Plug gauge acc. EN 60 947-1 A4
Cross connect channels 2
Cross section single wire from 0,5 mm²
Cross section single wire to 6 mm²
Cross section stranded wire from 0,6 mm²
Cross section stranded wire to 6 mm²
Cross section stranded with ferrule from 0,5 mm²
Cross section stranded with ferrule to 4 mm²
Rated wire cross section from (AWG) 20
Rated wire cross section to (AWG) 10
Stripping length 12 mm

Materials

Insulation material Polyamide 6.6
Flammability class UL94-V0
Operating temperature from -40 °C
Operating temperature to 120 °C

Approvals

Rated voltage CSA 600 V
Rated current CSA 28 A
CSA test standard C22.2 No 158
Rated voltage CSAus 600 V
Rated current CSAus 28 A
CSAus test standard UL 1059
EAC test standard TR ZU 004/2011
KEMA KEUR test standard EN 60947-7-1:2009

Additional data

Tariff code 85369010
Country of origin BG
Weight 8,25 g
Pack size 100