KTO 011 is an electro-magnetic thermostat with one NC contact for regulating, for example, heating elements. KTS 011 is an electro-magnetic thermostat with one NO contact for regulating, for example, filter fans or overheating alarms.
General data |
|
---|---|
Control range temperature from | 0 °C |
Control range temperature to | 60 °C |
Tolerance switch off | ±4K |
Tolerance for switch on | ±4K |
Hysteresis temperature | 7K |
Mounting | DIN-rail 35mm, quick mount |
Rated operating conditions |
|
Voltage max | 250 V ac |
Inrush max | 16 A |
Breaking capacity | 250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC |
Contact resistance | <20 mΩ |
Electrical lifetime | > 100 000 operations |
Connection type | 2-pole 1-strand: 2,5 mm² (AWG 14) or multistrand 1,5 mm² (AWG 16). Torque 0,8 Nm. |
Humidity | <90 % RH (non-condensing) |
Operational temperature | -45°C ... +80°C |
Storage temperature | -45°C ... +80°C |
Life span | > 1000 000 operations |
*Invisible Heading* |
|
---|---|
Dimensions |
|
Height | 60 mm |
Width | 33 mm |
Depth | 43 mm |
Weight | 0,04 kg |
Material plastic housing | Plastic |
Safety & approvals |
|
Plastic cover | Light grey plastic, UL94 V-0 |
IP class | IP20 |
Approvals | CE, EAC, RoHS, VDE |
Country of origin | Germany |
KTO 011 is an electro-magnetic thermostat with one NC contact for regulating, for example, heating elements. KTS 011 is an electro-magnetic thermostat with one NO contact for regulating, for example, filter fans or overheating alarms.
At OEM Automatic, we can supply a series of components for your one project. All under one roof. This case study discusses how we supplied several components for our customer's new electro-pneumatic control box.
To promote constant and reliable performance, as well as a longer life of parts in the vehicle, it is important to consider the right cable protector.
We have now added switch disconnectors to our range! Switch disconnectors contribute to the overall functionality and safety of electrical systems.
LOCC-Box from Lutze is an intelligent current monitoring device that provides reliable protection of DC circuits in a slimline 8.1mm housing.
OEM Automatic has integrated push-in technology into it's product offering for many years now. In this blog post, we'll explore the various benefits of push-in technology and some of the products we offer that make use of this innovation, such as push-in terminals, push-in sockets, and even push-in heaters.
We present Kublers ultimate package: Encoders and Process Displays, which can be used together to create efficient processes.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Control range temperature from | Control range temperature to | Control range temperature from | Control range temperature to | Mounting | Breaking capacity | Connection type | Humidity | Life span | Approvals | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
KTO 011 Thermostat, 0-60°C, normally closed
Art:
01140.0-00
Copied
|
0 °C
|
60 °C
|
|
|
DIN-rail 35mm, quick mount
|
250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC
|
2-pole 1-strand: 2,5 mm² (AWG 14) or multistrand 1,5 mm² (AWG 16). Torque 0,8 Nm.
|
<90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, EAC, RoHS, VDE
|
| ||
KTO 011 Thermostat, 0…60°C, normally closed , UL approved
Art:
01146.9-00
Copied
|
0 °C
|
60 °C
|
|
|
DIN-rail 35mm, quick mount
|
250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC
|
2-pole 1-strand: 2,5 mm² (AWG 14) or multistrand 1,5 mm² (AWG 16). Torque 0,8 Nm.
|
<90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTO 011 Thermostat, -10°C…+50°C, normally closed
Art:
01142.0-00
Copied
|
-10 °C
|
50 °C
|
|
|
DIN-rail mount EN60715
|
250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC
|
2-pole terminal for 2,5 mm² wires
|
Max. 90 % RH (non-condensing)
|
> 100 000 operations
|
CE, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTO 011 Thermostat, 20°C…80°C, normally closed
Art:
01159.0-00
Copied
|
20 °C
|
80 °C
|
|
|
DIN-rail 35mm, quick mount
|
|
|
Max. 90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTS 011 Thermostat, 0-60°C, normally open
Art:
01141.0-00
Copied
|
0 °C
|
60 °C
|
|
|
DIN-rail 35mm, quick mount
|
250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC
|
2-pole 1-strand: 2,5 mm² (AWG 14) or multistrand 1,5 mm² (AWG 16). Torque 0,8 Nm.
|
<90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, EAC, RoHS, VDE
|
| ||
KTS 011 Thermostat, 0…60°C, normally open , UL approved
Art:
01147.9-00
Copied
|
0 °C
|
60 °C
|
|
|
DIN-rail 35mm, quick mount
|
250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC
|
2-pole 1-strand: 2,5 mm² (AWG 14) or multistrand 1,5 mm² (AWG 16). Torque 0,8 Nm.
|
<90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTS 011 Thermostat, -10°C…+50°C, normally open
Art:
01143.0-00
Copied
|
-10 °C
|
50 °C
|
|
|
DIN-rail mount EN60715
|
250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC
|
2-pole terminal for 2,5 mm² wires
|
Max. 90 % RH (non-condensing)
|
> 100 000 operations
|
CE, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTS 011 Thermostat, 20°C…80°C, normally open
Art:
01158.0-00
Copied
|
20 °C
|
80 °C
|
|
|
DIN-rail 35mm, quick mount
|
250 VAC, 10 (2) A / 120 VAC, 15 (2) A. DC: 30W @ 24 VDC, up to 72 VDC
|
|
Max. 90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTO 011 Thermostat, 32°F…140°F, normally closed
Art:
01140.9-00
Copied
|
|
|
32 °F
|
140 °F
|
DIN-rail 35mm, quick mount
|
|
|
Max. 90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTS 011 Thermostat, 32°F…140°F, normally open
Art:
01141.9-00
Copied
|
|
|
32 °F
|
140 °F
|
DIN-rail 35mm, quick mount
|
|
|
Max. 90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTO 011 Thermostat, 14°F…122°F, normally closed
Art:
01142.9-00
Copied
|
|
|
14 °F
|
122 °F
|
DIN-rail 35mm, quick mount
|
|
|
Max. 90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
| ||
KTS 011 Thermostat, 14°F…122°F, normally open
Art:
01143.9-00
Copied
|
|
|
14 °F
|
122 °F
|
DIN-rail 35mm, quick mount
|
|
|
Max. 90 % RH (non-condensing)
|
> 1000 000 operations
|
CE, CSA, cULus, EAC, RoHS, UL E164102, VDE
|
|
Select a variant in the list