CONTA-CLIP
Test-disconnect terminals are mostly used in the sectors of electricity generation and supply.They are tailored to the variety of switching
demands for current-converter secondary circuits that predominate in these sectors. Current transformers must always have a secondary
circuit when electricity meters and measuring instruments are being replaced, or when making comparative measurements.
CONTA-CLIP test-disconnect terminals are available in the following three basic versions, each with or without a pre-assembled socket plug.
All versions provide touch-safe protection according to DGUV-3.
A captive, screw-on sliding partition is used to separate the current and voltage paths.
The switch position is always easy to detect since the disconnect screw has a yellow insulating sleeve.
Â
In all versions, the STB 14/4 socket plugs can be used for a test pick-off for measuring values using the PS 4 test plug or the conventional (4 mm) insulated test plugs.
Â
The VH 19 connecting sleeves and the BS 25 screws or STB 14/4 socket plugs are required for fastening the QVS cross-switches above the terminal block. The cross-switches  are available from 2 to 4 poles.
The QSB internal cross-switches are positioned within the terminal block and make contact over the sliding contact on the LT- or QT-terminals. The cross-switches are available from 2 to 4 poles.
The BS 25 mounting screws are used together with the VH 19 connecting sleeves to establish contact with the QVS cross-switches.
Â
General data |
|
---|---|
Rated wire cross section | 10 mm² |
Colour | Beige |
Rated voltage IEC | 400 V |
Rated current IEC | 10 A |
Mounting | TS 35 and TS 32 |
Rated impulse voltage | 4 kV |
Overvoltage category | III |
Contamination degree | 3 |
Approvals | CSA, CSA US |
Dimensions |
|
Length | 72 mm |
Width | 8 mm |
Height TS 35/7.5 | 47 mm |
Height TS 32 | 51,5 mm |
Connection data |
|
Connections | 2 |
Number of levels | 1 |
Plug gauge acc. EN 60 947-1 | A5 |
Cross connect channels | 2 |
Cross section single wire from | 0,2 mm² |
Cross section single wire to | 10 mm² |
Cross section stranded wire from | 0,2 mm² |
Cross section stranded wire to | 10 mm² |
Cross section stranded with ferrule from | 0,2 mm² |
Cross section stranded with ferrule to | 10 mm² |
*Invisible Heading* |
|
---|---|
Rated wire cross section from (AWG) | 8 |
Rated wire cross section to (AWG) | 22 |
Stripping length | 12 mm |
Screw size | M 4 |
Screw type | Slotted |
Torque min | 1,2 Nm |
Torque max | 2 Nm |
Materials |
|
Insulation material | Polyamide 6.6 |
Flammability class | UL94-V2 |
Operating temperature from | -40 °C |
Operating temperature to | 105 °C |
Approvals |
|
Rated voltage CSA | 600 V |
Rated current CSA | 45 A |
CSA test standard | C22.2 No 158 |
Rated voltage CSAus | 600 V |
Rated current CSAus | 45 A |
CSAus test standard | UL 1059 |
Additional data |
|
Tariff code | 85369010 |
Country of origin | DE |
Weight | 24,66 g |
Pack size | 50 |
Test-disconnect terminals are mostly used in the sectors of electricity generation and supply.They are tailored to the variety of switching
demands for current-converter secondary circuits that predominate in these sectors. Current transformers must always have a secondary
circuit when electricity meters and measuring instruments are being replaced, or when making comparative measurements.
CONTA-CLIP test-disconnect terminals are available in the following three basic versions, each with or without a pre-assembled socket plug.
All versions provide touch-safe protection according to DGUV-3.
A captive, screw-on sliding partition is used to separate the current and voltage paths.
The switch position is always easy to detect since the disconnect screw has a yellow insulating sleeve.
Â
In all versions, the STB 14/4 socket plugs can be used for a test pick-off for measuring values using the PS 4 test plug or the conventional (4 mm) insulated test plugs.
Â
The VH 19 connecting sleeves and the BS 25 screws or STB 14/4 socket plugs are required for fastening the QVS cross-switches above the terminal block. The cross-switches  are available from 2 to 4 poles.
The QSB internal cross-switches are positioned within the terminal block and make contact over the sliding contact on the LT- or QT-terminals. The cross-switches are available from 2 to 4 poles.
The BS 25 mounting screws are used together with the VH 19 connecting sleeves to establish contact with the QVS cross-switches.
Â
Renowned for high-quality cable cutting and crimping tools, Klauke serves electrical contractors, cable jointers, and linemen across a spectrum of sectors
At OEM Automatic, we can supply a series of components for your one project. All under one roof. This case study discusses how we supplied several components for our customer's new electro-pneumatic control box.Â
To promote constant and reliable performance, as well as a longer life of parts in the vehicle, it is important to consider the right cable protector.
We have now added switch disconnectors to our range! Switch disconnectors contribute to the overall functionality and safety of electrical systems.
LOCC-Box from Lutze is an intelligent current monitoring device that provides reliable protection of DC circuits in a slimline 8.1mm housing.
OEM Automatic has integrated push-in technology into it's product offering for many years now. In this blog post, we'll explore the various benefits of push-in technology and some of the products we offer that make use of this innovation, such as push-in terminals, push-in sockets, and even push-in heaters.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Rated wire cross section | Colour | Rated voltage IEC | Rated current IEC | Mounting | Rated impulse voltage | Overvoltage category | Contamination degree | Approvals | Additional information | Length | Width | Height TS 35/7.5 | Height TS 32 | Connections | Number of levels | Plug gauge acc. EN 60 947-1 | Cross connect channels | Number of test pick off options | Cross section single wire from | Cross section single wire to | Cross section stranded wire from | Cross section stranded wire to | Cross section stranded with ferrule from | Cross section stranded with ferrule to | Rated wire cross section from (AWG) | Rated wire cross section to (AWG) | Stripping length | Screw size | Screw type | Torque min | Torque max | Insulation material | Flammability class | Operating temperature from | Operating temperature to | Rated voltage CSA | Rated current CSA | CSA test standard | Rated voltage CSAus | Rated current CSAus | CSAus test standard | Tariff code | Country of origin | Weight | Pack size | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
PTK 10/LT , Test-disconnect terminal
Art:
1130.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35 and TS 32
|
4 kV
|
III
|
3
|
CSA, CSA US
|
|
72 mm
|
8 mm
|
47 mm
|
51,5 mm
|
2
|
1
|
A5
|
2
|
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
600 V
|
45 A
|
C22.2 No 158
|
600 V
|
45 A
|
UL 1059
|
85369010
|
DE
|
24,66 g
|
50
|
| ||
PTK 10/LT/STB, Test-disconnect terminal with sockets
Art:
1131.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35 and TS 32
|
4 kV
|
III
|
3
|
CSA, CSA US
|
with sockets
|
72 mm
|
8 mm
|
47 mm
|
51,5 mm
|
2
|
1
|
A5
|
|
2
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
600 V
|
45 A
|
C22.2 No 158
|
600 V
|
45 A
|
UL 1059
|
85369010
|
DE
|
28,9 g
|
50
|
| ||
PTK 10/QT, Test-disconnect terminal, separated perpendicularly
Art:
1132.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35 and TS 32
|
4 kV
|
III
|
3
|
CSA, CSA US
|
|
72 mm
|
8 mm
|
47 mm
|
51,5 mm
|
2
|
1
|
A5
|
2
|
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
600 V
|
45 A
|
C22.2 No 158
|
600 V
|
45 A
|
UL 1059
|
85369010
|
DE
|
25,14 g
|
50
|
| ||
PTK 10/QT, Test-disconnect terminal with sockets, separated perpendicularly
Art:
1133.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35 and TS 32
|
4 kV
|
III
|
3
|
CSA, CSA US
|
with sockets
|
72 mm
|
8 mm
|
47 mm
|
51,5 mm
|
2
|
1
|
A5
|
|
2
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
600 V
|
45 A
|
C22.2 No 158
|
600 V
|
45 A
|
UL 1059
|
85369010
|
DE
|
29,74 g
|
50
|
| ||
PTK 10/DU, Test-disconnect feed through terminal
Art:
1134.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35 and TS 32
|
4 kV
|
III
|
3
|
CSA, CSA US
|
|
72 mm
|
8 mm
|
47 mm
|
51,5 mm
|
2
|
1
|
A5
|
2
|
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
600 V
|
45 A
|
C22.2 No 158
|
600 V
|
45 A
|
UL 1059
|
85369010
|
DE
|
22,56 g
|
50
|
| ||
PTK 10/DU/STB,Test-disconnect feed through terminal with sockets
Art:
1135.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35 and TS 32
|
4 kV
|
III
|
3
|
CSA, CSA US
|
with sockets
|
72 mm
|
8 mm
|
47 mm
|
51,5 mm
|
2
|
1
|
A5
|
|
2
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
600 V
|
45 A
|
C22.2 No 158
|
600 V
|
45 A
|
UL 1059
|
85369010
|
DE
|
22,56 g
|
50
|
| ||
PTK 10/LT/HB, Test-disconnect terminal, Finger screw operated
Art:
17366.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35
|
4 kV
|
III
|
3
|
|
hand lever
|
72 mm
|
8 mm
|
63 mm
|
67,5 mm
|
2
|
1
|
A5
|
2
|
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
|
|
85369010
|
DE
|
31,66 g
|
50
|
| ||
PTK 10/LT/STB/HB, Test-disconnect terminal with sockets, Finger screw operated
Art:
17367.2
Copied
|
10 mm²
|
Beige
|
400 V
|
10 A
|
TS 35
|
4 kV
|
III
|
3
|
|
hand lever
|
72 mm
|
8 mm
|
63 mm
|
67,5 mm
|
2
|
1
|
A5
|
|
2
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
0,2 mm²
|
10 mm²
|
8
|
22
|
12 mm
|
M 4
|
Slotted
|
1,2 Nm
|
2 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
|
|
85369010
|
DE
|
35,86 g
|
50
|
| ||
CT- LINK Assembly Single Phase
Art:
820100000008
Copied
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CT - LINK 2 Assembly 3-Phase with voltage feed trough terminals
Art:
820100000009
Copied
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CT-LINK 3 Assembly 3-Phase with Voltage Disconnects
Art:
820100000010
Copied
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|