CONTA-CLIP
The DLI, DLIS range of installation terminals enable the ability to distribute power in a small footprint and gives the ability to disconnect the neutral connections.
Â
To comply to VDE 100 (IEC 364) and VDE 0108, which stipulates the requirement that a circuit's association must be clearly detectable.
Â
It is also required that an insulation test can be performed on each terminal without disconnecting the Neutral wire from the terminal blocks.
Â
This is a specific requirement for public buildings such as hospitals, schools, airports, office buildings and institutions.
Â
The terminals support the use of 10 x 3 busbar and is positioned on the outside of the terminals, the bar is held in place using the HP support plates. A sliding contact that contacts both sides of the busbar is used to connect and disconnect from the busbar.
Â
This sliding contact permits functional testing independent of the operational mode.
Â
Â
General data |
|
---|---|
Rated wire cross section | 2,5 mm² |
Colour | Beige |
Rated voltage IEC | 400 V |
Rated current IEC | 24 A |
Mounting | TS 35 |
Rated impulse voltage | 4 kV |
Overvoltage category | III |
Contamination degree | 3 |
Dimensions |
|
Length | 90,5 mm |
Width | 6 mm |
Height TS 35/7.5 | 53 mm |
Connection data |
|
Connections | 4 |
Special connections | Busbar 10 x 3mm |
Plug gauge acc. EN 60 947-1 | A3 |
Cross connect channels | 2 |
Cross section single wire from | 0,2 mm² |
Cross section single wire to | 4 mm² |
Cross section stranded wire from | 0,2 mm² |
Cross section stranded wire to | 4 mm² |
*Invisible Heading* |
|
---|---|
Cross section stranded with ferrule from | 0,2 mm² |
Cross section stranded with ferrule to | 2,5 mm² |
Rated wire cross section from (AWG) | 22 |
Rated wire cross section to (AWG) | 14 |
Stripping length | 8 mm |
Screw size | M 2,5 |
Screw type | Slotted |
Torque min | 0,4 Nm |
Torque max | 0,8 Nm |
Materials |
|
Insulation material | Polyamide 6.6 |
Flammability class | UL94-V2 |
Operating temperature from | -40 °C |
Operating temperature to | 105 °C |
Additional data |
|
Tariff code | 85369010 |
Country of origin | CZ |
Weight | 26,8 g |
Pack size | 50 |
Type of terminal | Screw Terminals, DIN Rail terminals |
The DLI, DLIS range of installation terminals enable the ability to distribute power in a small footprint and gives the ability to disconnect the neutral connections.
Â
To comply to VDE 100 (IEC 364) and VDE 0108, which stipulates the requirement that a circuit's association must be clearly detectable.
Â
It is also required that an insulation test can be performed on each terminal without disconnecting the Neutral wire from the terminal blocks.
Â
This is a specific requirement for public buildings such as hospitals, schools, airports, office buildings and institutions.
Â
The terminals support the use of 10 x 3 busbar and is positioned on the outside of the terminals, the bar is held in place using the HP support plates. A sliding contact that contacts both sides of the busbar is used to connect and disconnect from the busbar.
Â
This sliding contact permits functional testing independent of the operational mode.
Â
Â
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Rated wire cross section | Colour | Rated voltage IEC | Rated current IEC | Mounting | Rated impulse voltage | Overvoltage category | Contamination degree | Approvals | Additional information | Length | Width | Height TS 35/7.5 | Connections | Special connections | Plug gauge acc. EN 60 947-1 | Cross connect channels | Cross section single wire from | Cross section single wire to | Cross section stranded wire from | Cross section stranded wire to | Cross section stranded with ferrule from | Cross section stranded with ferrule to | Rated wire cross section from (AWG) | Rated wire cross section to (AWG) | Stripping length | Screw size | Screw type | Torque min | Torque max | Insulation material | Flammability class | Operating temperature from | Operating temperature to | CSA test standard | CSAus test standard | EAC test standard | KEMA KEUR test standard | Tariff code | Country of origin | Weight | Pack size | Type of terminal | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
DLIS 2.5 PE/L/NT, 2.5mm² installation terminal, PE, live, neutral, busbar
Art:
1410.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
Busbar 10 x 3mm
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
26,8 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 PE/L/N, 2.5mm² installation terminal, PE, live, neutral
Art:
1411.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
24,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 PE/L/L, 2.5mm² installation terminal, PE, live, live
Art:
1412.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
24,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L/N, 2.5mm² installation terminal, live, neutral
Art:
1413.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
14,04 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L/L, 2.5mm² installation terminal, live, live
Art:
1414.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
14,04 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 N, 2.5mm² installation terminal, neutral
Art:
1415.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
1
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
10,76 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L, 2.5mm² installation terminal, live
Art:
1416.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
1
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
10,76 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 PE/L/NT, 2.5mm² installation terminal, PE, live, neutral, slide
Art:
1417.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
28,76 g
|
50
|
|
| ||
DLI 2,5 PE/L/N, 2.5mm² installation terminal, PE, live, neutral,
Art:
1418.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009, EN 60947-7-2:2009
|
85369010
|
DE
|
26,08 g
|
50
|
|
| ||
DLI 2.5 PE/L/L, 2.5mm² installation terminal, PE, live, live
Art:
1419.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009, EN 60947-7-2:2009
|
85369010
|
CZ
|
26,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 L/N, 2.5mm² installation terminal, live, neutral
Art:
1420.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009
|
85369010
|
DE
|
16,08 g
|
50
|
|
| ||
DLI 2,5 L/L, 2.5mm² installation terminal, live, live
Art:
1421.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009
|
85369010
|
DE
|
16,08 g
|
50
|
|
| ||
DLI 2,5 N, 2.5mm² installation terminal, neutral
Art:
1422.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
|
85369010
|
DE
|
12,12 g
|
50
|
|
| ||
DLI 2,5 L, 2.5mm² installation terminal, live
Art:
1423.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
|
85369010
|
DE
|
12,12 g
|
50
|
|
| ||
DLIS 2.5 B-W, 2.5mm² installation 3-phase terminal block
Art:
1446.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
12
|
Busbar 10 x 3mm
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
80,43 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-D, 2.5mm² installation 3-phase terminal block
Art:
1447.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for 3-phase application
|
90,5 mm
|
12 mm
|
53 mm
|
8
|
Busbar 10 x 3mm
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
41,44 g
|
25
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 B-W, 2.5mm² installation terminal block, slide
Art:
1448.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
86,25 g
|
16
|
|
| ||
DLI 2,5 B-D, 2.5mm² installation 3-phase terminal block, slide
Art:
1449.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
block for 3-phase application
|
90,5 mm
|
12 mm
|
53 mm
|
9
|
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
44,63 g
|
25
|
|
| ||
DLI 2,5 D, 2.5mm² installation terminal, live
Art:
1490.2
Copied
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
DLIS 2.5 B-3L/3N/3PE, 2.5mm² installation terminal block, 3 x PE, 3 x live, 3 x neutral
Art:
2715.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
69,27 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-3L/N/PE, 2.5mm² installation terminal block, PE, 3 x live, neutral
Art:
2716.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for 3-phase application
|
90,5 mm
|
18 mm
|
53 mm
|
9
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
48,04 g
|
25
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-6L, 2.5mm² installation terminal block, 6 x live
Art:
2717.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
18 mm
|
53 mm
|
12
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
42,23 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-6L/3PE, 2.5mm² installation terminal block, 3 x PE, 3 x live
Art:
2718.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
72,23 g
|
16
|
Screw Terminals, DIN Rail terminals
|
|
Select a variant in the list
If you need any help, you can contact us in one of the following ways: