Important notice - We will be performing system maintenance from 4pm Friday 19th April. Whilst we are performing this maintenance there will be no pricing available or ability to place orders. This will last for 2-3 days. Please contact customer support for any enquiries 0116 284 9900. We apologise for any inconvenience caused.
CONTA-CLIP
The DLI, DLIS range of installation terminals enable the ability to distribute power in a small footprint and gives the ability to disconnect the neutral connections.
Â
To comply to VDE 100 (IEC 364) and VDE 0108, which stipulates the requirement that a circuit's association must be clearly detectable.
Â
It is also required that an insulation test can be performed on each terminal without disconnecting the Neutral wire from the terminal blocks.
Â
This is a specific requirement for public buildings such as hospitals, schools, airports, office buildings and institutions.
Â
The terminals support the use of 10 x 3 busbar and is positioned on the outside of the terminals, the bar is held in place using the HP support plates. A sliding contact that contacts both sides of the busbar is used to connect and disconnect from the busbar.
Â
This sliding contact permits functional testing independent of the operational mode.
Â
Â
General data |
|
---|---|
Rated wire cross section | 2,5 mm² |
Colour | Beige |
Rated voltage IEC | 400 V |
Rated current IEC | 24 A |
Mounting | TS 35 |
Rated impulse voltage | 4 kV |
Overvoltage category | III |
Contamination degree | 3 |
Dimensions |
|
Length | 90,5 mm |
Width | 6 mm |
Height TS 35/7.5 | 53 mm |
Connection data |
|
Connections | 4 |
Special connections | Busbar 10 x 3mm |
Plug gauge acc. EN 60 947-1 | A3 |
Cross connect channels | 2 |
Cross section single wire from | 0,2 mm² |
Cross section single wire to | 4 mm² |
Cross section stranded wire from | 0,2 mm² |
Cross section stranded wire to | 4 mm² |
*Invisible Heading* |
|
---|---|
Cross section stranded with ferrule from | 0,2 mm² |
Cross section stranded with ferrule to | 2,5 mm² |
Rated wire cross section from (AWG) | 22 |
Rated wire cross section to (AWG) | 14 |
Stripping length | 8 mm |
Screw size | M 2,5 |
Screw type | Slotted |
Torque min | 0,4 Nm |
Torque max | 0,8 Nm |
Materials |
|
Insulation material | Polyamide 6.6 |
Flammability class | UL94-V2 |
Operating temperature from | -40 °C |
Operating temperature to | 105 °C |
Additional data |
|
Tariff code | 85369010 |
Country of origin | CZ |
Weight | 26,8 g |
Pack size | 50 |
Type of terminal | Screw Terminals, DIN Rail terminals |
The DLI, DLIS range of installation terminals enable the ability to distribute power in a small footprint and gives the ability to disconnect the neutral connections.
Â
To comply to VDE 100 (IEC 364) and VDE 0108, which stipulates the requirement that a circuit's association must be clearly detectable.
Â
It is also required that an insulation test can be performed on each terminal without disconnecting the Neutral wire from the terminal blocks.
Â
This is a specific requirement for public buildings such as hospitals, schools, airports, office buildings and institutions.
Â
The terminals support the use of 10 x 3 busbar and is positioned on the outside of the terminals, the bar is held in place using the HP support plates. A sliding contact that contacts both sides of the busbar is used to connect and disconnect from the busbar.
Â
This sliding contact permits functional testing independent of the operational mode.
Â
Â
Renowned for high-quality cable cutting and crimping tools, Klauke serves electrical contractors, cable jointers, and linemen across a spectrum of sectors
At OEM Automatic, we can supply a series of components for your one project. All under one roof. This case study discusses how we supplied several components for our customer's new electro-pneumatic control box.Â
To promote constant and reliable performance, as well as a longer life of parts in the vehicle, it is important to consider the right cable protector.
We have now added switch disconnectors to our range! Switch disconnectors contribute to the overall functionality and safety of electrical systems.
LOCC-Box from Lutze is an intelligent current monitoring device that provides reliable protection of DC circuits in a slimline 8.1mm housing.
OEM Automatic has integrated push-in technology into it's product offering for many years now. In this blog post, we'll explore the various benefits of push-in technology and some of the products we offer that make use of this innovation, such as push-in terminals, push-in sockets, and even push-in heaters.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Rated wire cross section | Colour | Rated voltage IEC | Rated current IEC | Mounting | Rated impulse voltage | Overvoltage category | Contamination degree | Approvals | Additional information | Length | Width | Height TS 35/7.5 | Connections | Special connections | Plug gauge acc. EN 60 947-1 | Cross connect channels | Cross section single wire from | Cross section single wire to | Cross section stranded wire from | Cross section stranded wire to | Cross section stranded with ferrule from | Cross section stranded with ferrule to | Rated wire cross section from (AWG) | Rated wire cross section to (AWG) | Stripping length | Screw size | Screw type | Torque min | Torque max | Insulation material | Flammability class | Operating temperature from | Operating temperature to | CSA test standard | CSAus test standard | EAC test standard | KEMA KEUR test standard | Tariff code | Country of origin | Weight | Pack size | Type of terminal | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
DLIS 2.5 PE/L/NT, 2.5mm² installation terminal, PE, live, neutral, busbar
Art:
1410.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
Busbar 10 x 3mm
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
26,8 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 PE/L/N, 2.5mm² installation terminal, PE, live, neutral
Art:
1411.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
24,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 PE/L/L, 2.5mm² installation terminal, PE, live, live
Art:
1412.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
24,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L/N, 2.5mm² installation terminal, live, neutral
Art:
1413.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
14,04 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L/L, 2.5mm² installation terminal, live, live
Art:
1414.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
14,04 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 N, 2.5mm² installation terminal, neutral
Art:
1415.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
1
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
10,76 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L, 2.5mm² installation terminal, live
Art:
1416.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
1
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
10,76 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 PE/L/NT, 2.5mm² installation terminal, PE, live, neutral, slide
Art:
1417.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
28,76 g
|
50
|
|
| ||
DLI 2,5 PE/L/N, 2.5mm² installation terminal, PE, live, neutral,
Art:
1418.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009, EN 60947-7-2:2009
|
85369010
|
DE
|
26,08 g
|
50
|
|
| ||
DLI 2.5 PE/L/L, 2.5mm² installation terminal, PE, live, live
Art:
1419.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009, EN 60947-7-2:2009
|
85369010
|
CZ
|
26,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 L/N, 2.5mm² installation terminal, live, neutral
Art:
1420.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009
|
85369010
|
DE
|
16,08 g
|
50
|
|
| ||
DLI 2,5 L/L, 2.5mm² installation terminal, live, live
Art:
1421.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009
|
85369010
|
DE
|
16,08 g
|
50
|
|
| ||
DLI 2,5 N, 2.5mm² installation terminal, neutral
Art:
1422.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
|
85369010
|
DE
|
12,12 g
|
50
|
|
| ||
DLI 2,5 L, 2.5mm² installation terminal, live
Art:
1423.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
|
85369010
|
DE
|
12,12 g
|
50
|
|
| ||
DLIS 2.5 B-W, 2.5mm² installation 3-phase terminal block
Art:
1446.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
12
|
Busbar 10 x 3mm
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
80,43 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-D, 2.5mm² installation 3-phase terminal block
Art:
1447.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for 3-phase application
|
90,5 mm
|
12 mm
|
53 mm
|
8
|
Busbar 10 x 3mm
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
41,44 g
|
25
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 B-W, 2.5mm² installation terminal block, slide
Art:
1448.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
86,25 g
|
16
|
|
| ||
DLI 2,5 B-D, 2.5mm² installation 3-phase terminal block, slide
Art:
1449.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
block for 3-phase application
|
90,5 mm
|
12 mm
|
53 mm
|
9
|
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
44,63 g
|
25
|
|
| ||
DLI 2,5 D, 2.5mm² installation terminal, live
Art:
1490.2
Copied
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
DLIS 2.5 B-3L/3N/3PE, 2.5mm² installation terminal block, 3 x PE, 3 x live, 3 x neutral
Art:
2715.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
69,27 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-3L/N/PE, 2.5mm² installation terminal block, PE, 3 x live, neutral
Art:
2716.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for 3-phase application
|
90,5 mm
|
18 mm
|
53 mm
|
9
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
48,04 g
|
25
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-6L, 2.5mm² installation terminal block, 6 x live
Art:
2717.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
18 mm
|
53 mm
|
12
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
42,23 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-6L/3PE, 2.5mm² installation terminal block, 3 x PE, 3 x live
Art:
2718.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
72,23 g
|
16
|
Screw Terminals, DIN Rail terminals
|
|
Select a variant in the list
If you need any help, you can contact us in one of the following ways: