CONTA-CLIP
The DLI, DLIS range of installation terminals enable the ability to distribute power in a small footprint and gives the ability to disconnect the neutral connections.
Â
To comply to VDE 100 (IEC 364) and VDE 0108, which stipulates the requirement that a circuit's association must be clearly detectable.
Â
It is also required that an insulation test can be performed on each terminal without disconnecting the Neutral wire from the terminal blocks.
Â
This is a specific requirement for public buildings such as hospitals, schools, airports, office buildings and institutions.
Â
The terminals support the use of 10 x 3 busbar and is positioned on the outside of the terminals, the bar is held in place using the HP support plates. A sliding contact that contacts both sides of the busbar is used to connect and disconnect from the busbar.
Â
This sliding contact permits functional testing independent of the operational mode.
Â
Â
General data |
|
---|---|
Rated wire cross section | 2,5 mm² |
Colour | Beige |
Rated voltage IEC | 400 V |
Rated current IEC | 24 A |
Mounting | TS 35 |
Rated impulse voltage | 4 kV |
Overvoltage category | III |
Contamination degree | 3 |
Dimensions |
|
Length | 90,5 mm |
Width | 6 mm |
Height TS 35/7.5 | 53 mm |
Connection data |
|
Connections | 4 |
Special connections | Busbar 10 x 3mm |
Plug gauge acc. EN 60 947-1 | A3 |
Cross connect channels | 2 |
Cross section single wire from | 0,2 mm² |
Cross section single wire to | 4 mm² |
Cross section stranded wire from | 0,2 mm² |
Cross section stranded wire to | 4 mm² |
*Invisible Heading* |
|
---|---|
Cross section stranded with ferrule from | 0,2 mm² |
Cross section stranded with ferrule to | 2,5 mm² |
Rated wire cross section from (AWG) | 22 |
Rated wire cross section to (AWG) | 14 |
Stripping length | 8 mm |
Screw size | M 2,5 |
Screw type | Slotted |
Torque min | 0,4 Nm |
Torque max | 0,8 Nm |
Materials |
|
Insulation material | Polyamide 6.6 |
Flammability class | UL94-V2 |
Operating temperature from | -40 °C |
Operating temperature to | 105 °C |
Additional data |
|
Tariff code | 85369010 |
Country of origin | CZ |
Weight | 26,8 g |
Pack size | 50 |
Type of terminal | Screw Terminals, DIN Rail terminals |
The DLI, DLIS range of installation terminals enable the ability to distribute power in a small footprint and gives the ability to disconnect the neutral connections.
Â
To comply to VDE 100 (IEC 364) and VDE 0108, which stipulates the requirement that a circuit's association must be clearly detectable.
Â
It is also required that an insulation test can be performed on each terminal without disconnecting the Neutral wire from the terminal blocks.
Â
This is a specific requirement for public buildings such as hospitals, schools, airports, office buildings and institutions.
Â
The terminals support the use of 10 x 3 busbar and is positioned on the outside of the terminals, the bar is held in place using the HP support plates. A sliding contact that contacts both sides of the busbar is used to connect and disconnect from the busbar.
Â
This sliding contact permits functional testing independent of the operational mode.
Â
Â
Here, our customer requires control boxes for electricity metering systems. We leveraged our expertise to deliver easy-to-install, ready-to-use assemblies. We look forward to creating more of these bespoke control boxes for our customer.
This blog talks all things DC circuit protection including the key components: electronic circuit breakers, fuses and current monitoring devices. As well as how to choose the right protection.
Did you get a chance to visit IATECH at The Leicester Marriott Hotel? We had over 33 exhibitors and 8 fantastic Tech Talks throughout the day, Read all about the day, here.
To help experience the capabilities of Z+F machines first-hand, we provide an in-depth demonstration and workshop. These sessions will show the machines in action and allow you to understand their features and gain valuable insight into their operation and benefits.
We are thrilled to announce the launch of IATECH, THe Industrial Automation Technology expo at Leicester Marriott Hotel on 23rd October. The ultimate platform for showcasing our extensive product range and broad business areas, featuring over 50 leading suppliers under one roof!
The specialist vehicle industry can include automotive and EV, heavy vehicles such as agriculture and rail, and marine. This email takes you through some of the various products we offer for specialist vehicle applications.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Parts | Rated wire cross section | Colour | Rated voltage IEC | Rated current IEC | Mounting | Rated impulse voltage | Overvoltage category | Contamination degree | Approvals | Additional information | Length | Width | Height TS 35/7.5 | Connections | Special connections | Plug gauge acc. EN 60 947-1 | Cross connect channels | Cross section single wire from | Cross section single wire to | Cross section stranded wire from | Cross section stranded wire to | Cross section stranded with ferrule from | Cross section stranded with ferrule to | Rated wire cross section from (AWG) | Rated wire cross section to (AWG) | Stripping length | Screw size | Screw type | Torque min | Torque max | Insulation material | Flammability class | Operating temperature from | Operating temperature to | CSA test standard | CSAus test standard | EAC test standard | KEMA KEUR test standard | Tariff code | Country of origin | Weight | Pack size | Type of terminal | Price | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
DLIS 2.5 PE/L/NT, 2.5mm² installation terminal, PE, live, neutral, busbar
Art:
1410.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
Busbar 10 x 3mm
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
26,8 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 PE/L/N, 2.5mm² installation terminal, PE, live, neutral
Art:
1411.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
24,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 PE/L/L, 2.5mm² installation terminal, PE, live, live
Art:
1412.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
24,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L/N, 2.5mm² installation terminal, live, neutral
Art:
1413.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
14,04 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L/L, 2.5mm² installation terminal, live, live
Art:
1414.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
CZ
|
14,04 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 N, 2.5mm² installation terminal, neutral
Art:
1415.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
1
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
10,76 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 L, 2.5mm² installation terminal, live
Art:
1416.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
1
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
10,76 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 PE/L/NT, 2.5mm² installation terminal, PE, live, neutral, slide
Art:
1417.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
28,76 g
|
50
|
|
| ||
DLI 2,5 PE/L/N, 2.5mm² installation terminal, PE, live, neutral,
Art:
1418.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009, EN 60947-7-2:2009
|
85369010
|
DE
|
26,08 g
|
50
|
|
| ||
DLI 2.5 PE/L/L, 2.5mm² installation terminal, PE, live, live
Art:
1419.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
5
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009, EN 60947-7-2:2009
|
85369010
|
CZ
|
26,08 g
|
50
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 L/N, 2.5mm² installation terminal, live, neutral
Art:
1420.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009
|
85369010
|
DE
|
16,08 g
|
50
|
|
| ||
DLI 2,5 L/L, 2.5mm² installation terminal, live, live
Art:
1421.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, KEMA KUR, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
4
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
EN 60947-7-1:2009
|
85369010
|
DE
|
16,08 g
|
50
|
|
| ||
DLI 2,5 N, 2.5mm² installation terminal, neutral
Art:
1422.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
|
85369010
|
DE
|
12,12 g
|
50
|
|
| ||
DLI 2,5 L, 2.5mm² installation terminal, live
Art:
1423.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
CSA, CSA US, EAC
|
|
90,5 mm
|
6 mm
|
53 mm
|
2
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
C22.2 No 158
|
UL 1059
|
TR ZU 004/2011
|
|
85369010
|
DE
|
12,12 g
|
50
|
|
| ||
DLIS 2.5 B-W, 2.5mm² installation 3-phase terminal block
Art:
1446.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
12
|
Busbar 10 x 3mm
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
80,43 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-D, 2.5mm² installation 3-phase terminal block
Art:
1447.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for 3-phase application
|
90,5 mm
|
12 mm
|
53 mm
|
8
|
Busbar 10 x 3mm
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
41,44 g
|
25
|
Screw Terminals, DIN Rail terminals
|
| ||
DLI 2,5 B-W, 2.5mm² installation terminal block, slide
Art:
1448.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
3
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
86,25 g
|
16
|
|
| ||
DLI 2,5 B-D, 2.5mm² installation 3-phase terminal block, slide
Art:
1449.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
EAC
|
block for 3-phase application
|
90,5 mm
|
12 mm
|
53 mm
|
9
|
|
A3
|
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
TR ZU 004/2011
|
|
85369010
|
DE
|
44,63 g
|
25
|
|
| ||
DLI 2,5 D, 2.5mm² installation terminal, live
Art:
1490.2
Copied
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
DLIS 2.5 B-3L/3N/3PE, 2.5mm² installation terminal block, 3 x PE, 3 x live, 3 x neutral
Art:
2715.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for AC application
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
69,27 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-3L/N/PE, 2.5mm² installation terminal block, PE, 3 x live, neutral
Art:
2716.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
block for 3-phase application
|
90,5 mm
|
18 mm
|
53 mm
|
9
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
48,04 g
|
25
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-6L, 2.5mm² installation terminal block, 6 x live
Art:
2717.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
18 mm
|
53 mm
|
12
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
42,23 g
|
16
|
Screw Terminals, DIN Rail terminals
|
| ||
DLIS 2.5 B-6L/3PE, 2.5mm² installation terminal block, 3 x PE, 3 x live
Art:
2718.2
Copied
|
2,5 mm²
|
Beige
|
400 V
|
24 A
|
TS 35
|
4 kV
|
III
|
3
|
|
|
90,5 mm
|
18 mm
|
53 mm
|
15
|
|
A3
|
2
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
4 mm²
|
0,2 mm²
|
2,5 mm²
|
22
|
14
|
8 mm
|
M 2,5
|
Slotted
|
0,4 Nm
|
0,8 Nm
|
Polyamide 6.6
|
UL94-V2
|
-40 °C
|
105 °C
|
|
|
|
|
85369010
|
DE
|
72,23 g
|
16
|
Screw Terminals, DIN Rail terminals
|
|
Select a variant in the list