PULS

Redundant modules 20 A Dimension Series

Redundant module used with power supply unit to assure 24 V supply. The redundant module has two separate inputs with diodes that separate the power supply units. In the event of a fault on the secondary side of power supply 1, the diode will prevent power supply 2 from being short circuited. A system protected against internal power supply faults is attained that is especially well-suited in processes where downtime is costly. The redundant module can also be used in systems in which operation of sensitive loads is to be assured. Input 1 is connected to the main power supply that normally supplies loads and, for example, the PLC. Input 2 is connected to a smaller power supply that is only connected to the sensitive load, in this case the PLC. In the event of a fault to the main power supply or short circuit of the loads, the PLC will be supplied by the smaller power supply and incorrect process terminations are avoided. The redundant module is also well-suited when you want to separate the power supply units from the loads so as to avoid returned voltage, such as from motors and batteries. YRM2.diode has 2 relay outputs that indicate if voltage drops/is zero. The relay opens in the event of faults and the LED turns off. YRM2 is especially well-suited for Dimension C, which does not have relay outputs. If more than 10 A is required per channel, two redundant modules are connected, one for each power supply. Both inputs must be connected on each module.

Read more
  • 32 mm wide
  • Dual diodes
  • Relay indication of power supply status
  • Increases operational reliability

Selected variant

Selected variant

Technical data

Input data

Input voltage dc 24-48 V
Input voltage dc min 18 V DC
Input voltage dc max 60 V DC
Input current per channel max 10 A

Output data

Output voltage 24 V DC
Output current 20 A
Output current max 25 A

Dimensions

Width 32 mm
Height 124 mm
Depth 117 mm
Weight 0,35 kg

Other

Input / Output Separation Diode
Approvals ATEX, CB, CE, CSA, CSA US, GL, UL
IP class IP20
Material protection Aluminium
Series Dimension Y
Voltage drop over semiconductor 850 mV
Temperature min without derating -40 °C
Temperature max without derating 70 °C
Type Power Supply Redundancy modules
DC relay output Yes

Product description

Redundant module used with power supply unit to assure 24 V supply. The redundant module has two separate inputs with diodes that separate the power supply units. In the event of a fault on the secondary side of power supply 1, the diode will prevent power supply 2 from being short circuited. A system protected against internal power supply faults is attained that is especially well-suited in processes where downtime is costly. The redundant module can also be used in systems in which operation of sensitive loads is to be assured. Input 1 is connected to the main power supply that normally supplies loads and, for example, the PLC. Input 2 is connected to a smaller power supply that is only connected to the sensitive load, in this case the PLC. In the event of a fault to the main power supply or short circuit of the loads, the PLC will be supplied by the smaller power supply and incorrect process terminations are avoided. The redundant module is also well-suited when you want to separate the power supply units from the loads so as to avoid returned voltage, such as from motors and batteries. YRM2.diode has 2 relay outputs that indicate if voltage drops/is zero. The relay opens in the event of faults and the LED turns off. YRM2 is especially well-suited for Dimension C, which does not have relay outputs. If more than 10 A is required per channel, two redundant modules are connected, one for each power supply. Both inputs must be connected on each module.

Accessories

Related products

Related

Parts Input voltage dc Input voltage dc min Depth Weight DC relay output Price
12-48 V
9 V DC
102 mm
0,29 kg
24-48 V
18 V DC
117 mm
0,35 kg
Yes

Selected variant

Select a variant in the list

Contact us

If you need any help, you can contact us in one of the following ways:

phone 0116 284 9900

Send an e-mail Send an e-mail