Power supply 1-phase, 12 V dc Dimension C Series, Generation 2

Puls Dimension C-series stands for cost optimization without compromising quality, reliability or performance.

CP10 is the second generation C-series 1-phase that sets new records by using the latest technology and sophisticated thermal design. With an efficiency of 94.3%, the power losses are very small and thus the width is reduced down to 39 mm. The efficiency is also very high at lower loads which is the normal operating condition. The mean value is on the whole 93.3% at 230 V ac.

Power boost of 20% enables higher current extraction without voltage drops. This is especially useful during start-ups and to bridge the current peaks in the application. The power reserve can be used continuously up to + 45°C and short periods from +45°C to +60°C.

Short-circuit currents. CP10 can provide short circuit current which is 3 times the nominal current for at least 12 ms, which helps secondary fuses and achieve selectivity. For more information see under Sec. fuses.

Hiccup Plus

With Pulse new short circuit technology ensures optimum protection. The unit leaves a very high short circuit that solves secondary fuses and provide sufficient starting current for example dc motors. If the output voltage drops below 6.5 V dc, a continuous current of 25 A is given for 2 seconds, then turn the assembly of the end to make a new restart attempt after about 18 seconds. This is done until the error has been corrected. This feature ensures a high short-circuit / overload current while avoiding a constant high current that can lead to thermal problems with cables and component damage.

More technical advantages. CP10 has active power factor correction (PFC) and actively protect inrush that effectively reduces start currents which are ideal if several units are connected in the same phase or if the supply is current limited through example. AC UPS. The protection is always active, regardless of the temperature. DC-OK output, wide temperature range, a large number of approvals and transient filter which ensures operation in an interference rich electrical environment makes the unit suitable for virtually all installations. CP10.121 also has an input where the signal turns off the unit.

 

 

Wiring

A: Primary side/control voltage

 

B: Secondary. Output voltage

 

C: potentiometer adjustable output voltage 12-15 V dc

 

D: DC OK LED. Lights when the voltage is 90% of the set value

 

E: DC-OK relay output. Closes when the output voltage is OK

 

F: Inputs for remote shutdown of the unit

Sec. fuses

Breakers is the most common type of fuse for ac voltage but is also used for dc voltages. Power supply always has a current limitation compared with an electricity network which hampers tripping of a circuit breaker of the magnetic field, especially if the voltage is as low as 12 V dc. Greater consideration must be given to the cable diameter and cable lengths. This even if the power supply is able to deliver high short circuit currents. For long cables and/or thin cable area so the solution is electronic fuses.

 

Puls CP10.121 have high short-circuit currents which enables tripping within 10 ms of length and cable section is as below specification.

 

 

Safe tripping of circuit breakers with different cable lengths/diameter

Short-circuit currents. Figure 3-2

 

0.75 mm2

1.0 mm2

1.5 mm2

2.5 mm2

Short circuit currents

C-2A

11 m

15 m

22 m

35 m

C-3A

9 m

13 m

18 m

23 m

C-4A

5 m

8 m

12 m

17 m

C-6A

-

1 m

2 m

3 m

B-6A

6 m

11 m

15 m

23 m

B-10A

2 m

3 m

3 m

4 m

B-13A

1 m

2 m

3 m

4 m

 

Hiccup function Fig 3-3

Hiccup function

Description of Hiccup plus function

Thanks to the unique Pul Hiccupplus ensures a high short circuit current while avoiding the risk of overheated cables and damage to the connected loads. When a short circuit occurs following.

  1. High peak power that enables tripping in 12 ms Figure 3-2.
  2. The unit leaves 25 A for 2 s.
  3. After 2 seconds the unit shuts off, then try to restart every 18 seconds. If the fault is removed, the unit starts automatically, otherwise it will lose further 18 s. The operation does not burden the cabling and does not cause damage to the electronics.  

 

Read more
  • Output current of 16 A
  • Up to 94% efficiency
  • Only 39 mm wide
  • Active current inrush protection

Selected variant

Selected variant

Technical data

Input data

Input voltage ac 100-240 V
Input voltage ac min 90 V AC
Input voltage ac max 264 V AC
Input voltage dc 110-150 V
Input voltage dc min 88 V DC
Input voltage dc max 180 V DC
Inrush current at 120 V ac typical 6 A
Inrush current at 230 V ac typical 9 A
Input voltage range Wide-range
Power factor at 120 V ac, full load. Typical 0,99
Power factor at 230 V ac, full load. Typical 0,96
Number of phases 1

Output data

Output voltage 12 V DC
Output voltage min 12 V DC
Output voltage max 15 V DC
Output current 16 A
Power 192 W

Efficiency / Lifetime / MTBF

Efficiency at 120 V ac, full load, typical 92,8 %
Efficiency at 230 V ac, typical 93,3 %
Efficiency at 230 V ac, full load, typical 94,3 %
Lifetime at 120 V ac, full load and +40 ° C 75000 h
Lifetime at 230 V ac, full load and +40 ° C 97000 h
MTBF (IEC 61709) 230 V ac, max load, 40 ° C 690000 h

Dimensions

Width 39 mm
Height 124 mm
Depth 117 mm
Weight 0,6 kg

Other

Approvals ABS, CB, CE, CSA, EX, GL, IECEx, UL
Hold time at 120 V ac, typical full load 50 ms
Hold time at 230 V ac, typical full load 50 ms
IP class IP20
Clamp type Screw
Material protection Aluminium
Supply frequency 50-60 ±6 %
Ripple max 50 mV pp
Series Dimension C
Power consumption 120 V ac 1,74 A
Power consumption 230 V ac 0,92 A
Power drop from +60 °C to + 70 °C 4,8 W/°C
Temperature min without derating -25 °C
Temperature max without derating 60 °C
Type Power Supply AC-DC
DC relay output Yes
Active Transient Yes

Product description

Puls Dimension C-series stands for cost optimization without compromising quality, reliability or performance.

CP10 is the second generation C-series 1-phase that sets new records by using the latest technology and sophisticated thermal design. With an efficiency of 94.3%, the power losses are very small and thus the width is reduced down to 39 mm. The efficiency is also very high at lower loads which is the normal operating condition. The mean value is on the whole 93.3% at 230 V ac.

Power boost of 20% enables higher current extraction without voltage drops. This is especially useful during start-ups and to bridge the current peaks in the application. The power reserve can be used continuously up to + 45°C and short periods from +45°C to +60°C.

Short-circuit currents. CP10 can provide short circuit current which is 3 times the nominal current for at least 12 ms, which helps secondary fuses and achieve selectivity. For more information see under Sec. fuses.

Hiccup Plus

With Pulse new short circuit technology ensures optimum protection. The unit leaves a very high short circuit that solves secondary fuses and provide sufficient starting current for example dc motors. If the output voltage drops below 6.5 V dc, a continuous current of 25 A is given for 2 seconds, then turn the assembly of the end to make a new restart attempt after about 18 seconds. This is done until the error has been corrected. This feature ensures a high short-circuit / overload current while avoiding a constant high current that can lead to thermal problems with cables and component damage.

More technical advantages. CP10 has active power factor correction (PFC) and actively protect inrush that effectively reduces start currents which are ideal if several units are connected in the same phase or if the supply is current limited through example. AC UPS. The protection is always active, regardless of the temperature. DC-OK output, wide temperature range, a large number of approvals and transient filter which ensures operation in an interference rich electrical environment makes the unit suitable for virtually all installations. CP10.121 also has an input where the signal turns off the unit.

 

 

Wiring

A: Primary side/control voltage

 

B: Secondary. Output voltage

 

C: potentiometer adjustable output voltage 12-15 V dc

 

D: DC OK LED. Lights when the voltage is 90% of the set value

 

E: DC-OK relay output. Closes when the output voltage is OK

 

F: Inputs for remote shutdown of the unit

Sec. fuses

Breakers is the most common type of fuse for ac voltage but is also used for dc voltages. Power supply always has a current limitation compared with an electricity network which hampers tripping of a circuit breaker of the magnetic field, especially if the voltage is as low as 12 V dc. Greater consideration must be given to the cable diameter and cable lengths. This even if the power supply is able to deliver high short circuit currents. For long cables and/or thin cable area so the solution is electronic fuses.

 

Puls CP10.121 have high short-circuit currents which enables tripping within 10 ms of length and cable section is as below specification.

 

 

Safe tripping of circuit breakers with different cable lengths/diameter

Short-circuit currents. Figure 3-2

 

0.75 mm2

1.0 mm2

1.5 mm2

2.5 mm2

Short circuit currents

C-2A

11 m

15 m

22 m

35 m

C-3A

9 m

13 m

18 m

23 m

C-4A

5 m

8 m

12 m

17 m

C-6A

-

1 m

2 m

3 m

B-6A

6 m

11 m

15 m

23 m

B-10A

2 m

3 m

3 m

4 m

B-13A

1 m

2 m

3 m

4 m

 

Hiccup function Fig 3-3

Hiccup function

Description of Hiccup plus function

Thanks to the unique Pul Hiccupplus ensures a high short circuit current while avoiding the risk of overheated cables and damage to the connected loads. When a short circuit occurs following.

  1. High peak power that enables tripping in 12 ms Figure 3-2.
  2. The unit leaves 25 A for 2 s.
  3. After 2 seconds the unit shuts off, then try to restart every 18 seconds. If the fault is removed, the unit starts automatically, otherwise it will lose further 18 s. The operation does not burden the cabling and does not cause damage to the electronics.  

 

Accessories

Related products

Related

Parts Input voltage ac min Input voltage dc Input voltage dc max Inrush current at 120 V ac typical Inrush current at 230 V ac typical Power factor at 120 V ac, full load. Typical Power factor at 230 V ac, full load. Typical Output current Power Efficiency at 120 V ac, full load, typical Efficiency at 230 V ac, typical Efficiency at 230 V ac, full load, typical Lifetime at 120 V ac, full load and +40 ° C Lifetime at 230 V ac, full load and +40 ° C MTBF (IEC 61709) 230 V ac, max load, 40 ° C Width Depth Weight Approvals Hold time at 120 V ac, typical full load Hold time at 230 V ac, typical full load Power consumption 120 V ac Power consumption 230 V ac Power drop from +60 °C to + 70 °C Price
85 V AC
110-150 V
180 V DC
4 A
4 A
0,98
0,91
10 A
120 W
93,2 %
92,3 %
94 %
94000 h
110000 h
32 mm
102 mm
0,44 kg
ATEX, CE, cULus, IECEx, IEC 62368-1:2018
35 ms
35 ms
1,09 A
0,6 A
3 W/°C
90 V AC
110-150 V
180 V DC
6 A
9 A
0,99
0,96
16 A
192 W
92,8 %
93,3 %
94,3 %
75000 h
97000 h
690000 h
39 mm
117 mm
0,6 kg
ABS, CB, CE, CSA, EX, GL, IECEx, UL
50 ms
50 ms
1,74 A
0,92 A
4,8 W/°C
90 V AC
110-300 V
360 V DC
6 A
9 A
0,99
0,96
16 A
192 W
92,8 %
93,3 %
94,3 %
75000 h
97000 h
690000 h
39 mm
117 mm
0,6 kg
CE, cULus
50 ms
50 ms
1,74 A
0,92 A
4,8 W/°C